Configurable Safety System SAFEMASTER PRO
21
0265525 / 16.05.19 en / 101A
Connection Terminals input module UG 6913.08, with 8 inputs
Connection Terminals Output module OSSD UG 6912.04, with 4 OSSD
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24 V DC power supply
-
2
NODE_SEL0
Input
Node selection
Input („Type 2“ acc. to EN 61131-2)
3
NODE_SEL1
Input
Input („Type 2“ acc. to EN 61131-2)
4
0VDC
-
0 V DC power supply
-
5
INPUT1
Input
Digital input 1
Input („Type 2“ acc. to EN 61131-2)
6
INPUT2
Input
Digital input 2
Input („Type 2“ acc. to EN 61131-2)
7
INPUT3
Input
Digital input 3
Input („Type 2“ acc. to EN 61131-2)
8
INPUT4
Input
Digital input 4
Input („Type 2“ acc. to EN 61131-2)
9
OUT_TEST1
Output
Short circuit detection output
PNP active high
10
OUT_TEST2
Output
Short circuit detection output
PNP active high
11
OUT_TEST3
Output
Short circuit detection output
PNP active high
12
OUT_TEST4
Output
Short circuit detection output
PNP active high
13
INPUT5
Input
Digital input 5
Input („Type 2“ acc. to EN 61131-2)
14
INPUT6
Input
Digital input 6
Input („Type 2“ acc. to EN 61131-2)
15
INPUT7
Input
Digital input 7
Input („Type 2“ acc. to EN 61131-2)
16
INPUT8
Input
Digital input 8
Input („Type 2“ acc. to EN 61131-2)
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24 V DC power supply
-
2
NODE_SEL0
Input
Node selection
Input („Type 2“ acc. to EN 61131-2)
3
NODE_SEL1
Input
Input („Type 2“ acc. to EN 61131-2)
4
0VDC
-
0 V DC power supply
-
5
OSSD1_A
Output
Static output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback / Restart 1
Input („Type 2“ acc. to EN 61131-2)
8
OUT_STATUS1
Output
Programmable signal output
PNP active high
9
OSSD2_A
Output
Static output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback / Restart 2
Input („Type 2“ acc. to EN 61131-2)
12
OUT_STATUS2
Output
Programmable signal output
PNP active high
13
24VDC
-
24 V DC power supply
24 V DC power supply-Ausgänge *
14
24VDC
-
24 V DC power supply
15
0VDC
-
0 V DC power supply
0 V DC power supply-Ausgänge *
16
0VDC
-
0 V DC power supply
17
OSSD4_A
Output
Static output 4
PNP active high
18
OSSD4_B
Output
PNP active high
19
RESTART_FBK4
Input
Feedback / Restart 4
Input („Type 2“ acc. to EN 61131-2)
20
OUT_STATUS4
Output
Programmable signal output
PNP active high
21
OSSD3_A
Output
Static output 3
PNP active high
22
OSSD3_B
Output
PNP active high
23
RESTART_FBK3
Input
Feedback / Restart 3
Input („Type 2“ acc. to EN 61131-2)
24
OUT_STATUS3
Output
Programmable signal output
PNP active high