Configurable Safety System SAFEMASTER PRO
45
0265525 / 16.05.19 en / 101A
OUTPUT MODULE RELAY UG 6914.04/000 AND UG 6914.04/008
Type::
UG 6914.04/000
UG 6914.04/008
SFF:
IEC 61508: 2
nd
edition
99.9 %
99.9 %
PFH
d
:
2.90E-9
2.94E-9
DC
avg
:
EN ISO 13849-1: 2008
99.0 %
98.9 %
MTTF
d
:
998.56
980.78
Nominal voltage:
24 V DC
±
20 % / PELV, PREDective Class III; UL: Supply from class 2 (LVLE)
Nominal consumption:
Max. 3 W
Switching voltage:
240 V AC
Minimum switching voltage
10 V DC
Switching current:
Max. 6 A
Minimum switching current:
20 mA
Contacts:
4 NO contacts
Input FBK/RESTART
(No. / description):
EDM control / possible Automatic or Manual operation with RESTART button
„Type 2“ acc. to EN 61131-2, IN: 7 to 10 mA at DC 24 V
Response time:
Response time (UG 6911, UG 6912, UG 6916) + 12 ms
Mechanical life:
> 20 x 10
6
B10
d
:
AC15 230V:
I = 3 A: 300,000
I = 1 A: 750,000
DC13 24V:
I
≤
2 A: 10,000,000
Digital status outputs (No. / description):
0
8
Programmable - PNP active high; max. 100 mA at 24 V DC
Connection to control unit
Proprietary 5-pole DOLD IN-RAIL-BUS
UL-Data, Switching capacity:
Each relay output: 250 V, 6 A, resistive
Weight:
250 g
250 g
Approvals:
Bemerkung
:
For each Relay output must be added to the previous PFH
d
a value that depends on the load of the relay and its
switching frequency.
In addition, the PL obtained from the Relay outputs changes depending on the configuration chosen by the user.
We assume N
op
defines the number of commutations / year