Configurable Safety System SAFEMASTER PRO
95
0265525 / 16.05.19 en / 101A
Parameters
Configuration with 2 dual channel outputs (Cat. 4)
Configuration with 4 single outputs (Cat. 4)
Manual Reset:
If selected this enables the request to reset each time the input signal falls. Otherwise, enabling of the output
directly follows the input conditions.
There are two types of reset: Manual and Monitored. When Manual is selected the system only verifies the
signal's transition from 0 to 1. If Monitored is selected the double transition from 0 to 1 and then back to 0 is
verified.
Enable Status:
If selected, the connection of the current OSSD state to any point on the screen is enabled.
K external time check:
If selected, enables the setting of the time window within which the external feedback signal is to be monitored
(according to output conditions).
With high level (TRUE) OUTPUT, the FBK signal must be at low level (FALSE) and vice versa, within the set
time. Ohterwise, OUTPUT is set to low level (FALSE) and the error is indicated on the control unit UG 6911 by
the flashing CLEAR LED of the corresponding OSSD error.