Configurable Safety System SAFEMASTER PRO
194
0265525 / 16.05.19 en / 101A
Application example of graphic simulation
The following example refers to the use of a press located inside a safety area. The motor of the press can only
be started when two conditions are simultaneously true: the safety area gate is closed and the command to start
the motor is sent. The motor will start two seconds after the start signal is sent.
Diagram
In the diagram the input elements are the safety area gate and the motor start command. These two signals are
used as the input for an AND logic operator the result of which will be delayed by two seconds by a retarder block.
The delayed signal will then energize the relay which will, in turn, allow the press motor to be started.
Diagram referring to the application example
Stimuli File
The stimuli file provide the closure oft he gate when 2000 ms have elapsed (signal set to LL1) and the start
command sent by the operator when 3000 ms have elapsed (signal set to LL1).
Stimuli file referring to the application example
Description of the menu items