FEATURES
5.18.3
PROGRAMMING REQUIREMENTS AND FLEXIBILITY
The digital inputs and outputs listed in Table 5-60 can be programmed.
Parameter
Group
Parameter / Description
Setting
12
Optimized Idle Enable
1 = Enable
8
Vehicle Speed Sensor
4 = Magnetic Pickup
13
3 01 AI Selection
0 = No Sensor
2 = OI Thermostat
13
Trans Neutral Input Con
fi
g
0 = Hardwired (man8al trans)
1 = J1939 (J1939 trans)
13
Park Brake Switch Con
fi
g
0
13
4 18 DI Selection
2 = Enable Engine Hood
35
4 09 DO Selection
10 = OI Active Lamp
35
4 10 DO Selection
3 = Vehicle Power Shutdown
35
3 17 DO Selection
4 = OI Alarm
17
Enable Idle Shutdown
1 = Enable with Park Brake
17
Enable PTO Shutdown
1 = Enable with park Brake
MCM
Starter Type Control
1 = Starter Activated via MCM
13
1 02 DI Selection
1 = Enable
35
3 17 DO Fault Detection
1 = Enable
35
4 09 DO Fault Detection
1 = Enable
35
4 10 DO Fault Detection
1 = Enable
17
Enable Idle PTO Shtn Override
0 = Disable
Table 5-60
Optimized Idle Digital Inputs and Digital Outputs
Optimized Idle options for battery charging and continuous run are listed in Table 5-61.
Parameter
Description
Range
Default
OI Continuous Batt
Time Enable
When enabled and OI has started the engine for battery
three consecutive times, the engine will run continuously
in OI Mode
0 = Disable
1 = Enable
0 = Disable
OI Variable Volt Thres
Enable
When enabled, the battery voltage threshold will be based
on ambient air temperature.
0 = Disable
1 = Enable
0 = Disable
OI Alternate Battery
Run Time
Sets the alternate run time for battery starts.
20 min to 2 hrs
0 min
OI Upper Limit
Continuous Run Temp
Set the continuous run upper limit. When the ambient
air temperature is above this limit, the engine will run
continuously.
40°C-100°C
32°C
OI Lower Limit
Continuous Run
Sets the continuous run lower limit. When the ambient
air temperature is below this limit, the engine will run
continuously.
40°C-100°C
—4°C
OI Thermostat Max
Time
Maximum amount of time the engine can run in
Thermostat Mode.
0–459000 sec
0 sec
OI Target Engine RPM
Sets the speed the engine will operate at in OI Mode.
800–1100 rpm
1100 rpm
Table 5-61
Optimized Idle Options
5-110
All information subject to change without notice.