10. Settings
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
60
10.10.3 Constant Power Factor cos φ
Menu
520 Reactive PwCtrl
Description
Allows a constant cos φ power factor to be configured.
Accessing the Menu
Main Menu > User Settings > Reactive PwCtrl
➔
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select
User
Settings
and then press the
button.
for assistance.
Ask your installer
energy production.
Changes could affect
2. Press the button to confirm.
➔
-------------------
Reactive PwCtrl
Active PwCtrl
-------------------
500
User settings
3. Press the
buttons to se-
lect
Reactive PwCtrl
and then
press the button.
➔
Cos phi: ind 1.00
Mode: Fix. cosPhi
-------------------
520 Reactive PwCtrl
4. Press the
buttons to
select
Mode
and then press
the button.
➔
Cos phi: ind 1.00
Mode: Fix. cosPhi
-------------------
520 Reactive PwCtrl
5. Press the
buttons to set
Mode
to
Cos phi (P)
and then
press the button.
➔
-------------------
Cos phi: ind 1.00
Mode: Fix. cosPhi
-------------------
520 Reactive PwCtrl
6. Press the
buttons to
select the parameter
Cos Phi
.
Press the button to change
the value.
Configurable Parameters
Display Text
Designation
Description
Cos Phi
cos φ
Defines cos φ to be the set
value.
inductive | capacitive
1 - 0.8
10.11 Local Control (Italy only)
nOTE
This function is only available for the
IT BT 21
grid.
Menu
500 User Settings
Description
In accordance with CEI 0-21:2012-06, the integrated grid and sys-
tem protection (SPI) can be activated or deactivated for PV sys-
tems equal to or lower than 6 kW.
Accessing the Menu
Main Menu > Options > Grounding
➔
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select
User
Settings
and then press the
button.
➔
-------------------
Local control: Off
-------------------
500 User settings
2. To change the setting, press
the button and then change
the value using the
buttons.
Configurable Parameters
Display Text
Designation
Description
Local control
Local control
On | Off
On = Parameter as per
CEI 0-21:2012-06 Sect. 8.6
nOTE
The parameters that must be configured under
CEI 0-21:2012-06 can be changed using the
Delta service software.