Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
8. Commissioning
EN
➔
ID: 1
Select RS485 ID
9. Press the
buttons to select the
ID
and then press
the button.
→ The data is then verified and loaded.
A message is displayed when the loading process is
successful.
nOTE
: If the message
Pendrive
error
is displayed, make sure the
USB drive is properly inserted or that
the file is not damaged.
Press ENTER
Successful
Load data
10. Press the button to confirm.
→ If the asymmetrical grid load balancing was acti-
vated on the solar inverter from which the data was
loaded, the following message appears.
activated
Power balancing is
→ If active or apparent power limitation was activated
on the solar inverter from which the data was
loaded, the following message appears.
##.#W/##.#kVA
been limited to
of that inverter has
The maximum power
11. If the above mentioned messages appear, press the
button to confirm each.
➔
-------------------
No
Yes
-------------------
Change loaded values
12. Press the
buttons to select
No
and then press the
button.
→ The
Date and Time
menu is displayed.
nOTE
: If you wish to change the
loaded values, select Yes. Commis-
sioning then continues with the grid
selection and is the same as the initial
commissioning.
➔
Time: 14:26:51
Date: 25.05.2012
-------------------
Date and time
13. To change the value, press the button and then set
the value using the
buttons. Press the button to
apply the value.
➔
continue
Time: 14:26:51
Date: 25.05.2012
-------------------
-------------------
Date and time
14. Press the
buttons to select
continue
and then
press the button.
→ The
RS485
menu is displayed.
➔
Baudrate: 19200
ID: 1
-------------------
RS485
15. To change the value, press the button and then set
the value using the
buttons. Press the button to
apply the value.
nOTE
: If multiple solar inverters are
to be connected via RS485, select a
different ID for each inverter. The ID
is also used when saving and loading
settings in order to identify the solar
inverter.
Available IDs:
1 - 254
Available baudrates:
2400 | 4800 | 9600 | 19200 | 38400
➔
continue
Baudrate: 19200
ID: 1
-------------------
-------------------
RS485
16. Press the
buttons to select
continue
and then
press the button.
→ The completion screen will be displayed.