Chapter 6 Control Modes of Operation
Revision September 2013
6-31
When increasing the setting value of P2-44 and P2-46 manually, ensure to pay close attention on
the setting value of P2-44 and P2-46. If the value of P2-44 and P2-46 is greater than 0, it indicates
that the corresponding resonance frequency of P2-43 and P2-45 is found through auto resonance
suppression function. If the value of P2-44 and P2-46 is equal to 0, it indicates that the value of P2-
43 and P2-45 will be the default value 1000 and this is not the frequency found by auto resonance
suppression function. At this time, if the users increase the value of notch filter attenuation rate
which does not exist, the performance of the current mechanical system may deteriorate.
Settings of P2-47
Current Value
Desired Value
Function
0 1
Clear the setting value of P2-43 ~ P2-46 and enable
auto resonance suppression function.
0 2
Clear the setting value of P2-43 ~ P2-46 and enable
auto resonance suppression function.
1 0
Save the setting value of P2-43 ~ P2-46 and disable
auto resonance suppression function.
1 1
Clear the setting value of P2-43 ~ P2-46 and enable
auto resonance suppression function.
1 2
Do not clear the setting value of P2-43 ~ P2-46 and
enable auto resonance suppression function
continuously.
2 0
Save the setting value of P2-43 ~ P2-46 and disable
auto resonance suppression function.
2 1
Clear the setting value of P2-43 ~ P2-46 and enable
auto resonance suppression function.
2 2
Do not clear the setting value of P2-43 ~ P2-46 and
enable auto resonance suppression function
continuously.