9-28 Process Control
Option:
Function:
[1]
*
Enable
cyclic
master
Enables process control via PROFIBUS master class
1 and disables process control via standard
fieldbus or PROFIBUS master class 2.
9-44 Fault Message Counter
Range:
Function:
0
*
[0 -
65535 ]
Indicates the number of fault events presently
stored in
. The buffer
capacity is maximum 8 error events. The buffer
and counter are set to 0 by reset or power-up.
9-45 Fault Code
Range:
Function:
0
*
[0 - 0 ] This buffer contains the alarm word for all alarms
and warnings that have occurred since last reset or
power-up. The buffer capacity is maximum 8 error
events.
9-47 Fault Number
Range:
Function:
0
*
[0 - 0 ] This buffer contains the alarm word for all alarms
and warnings that have occurred since last reset or
power-up. The buffer capacity is maximum 8 error
events.
9-52 Fault Situation Counter
Range:
Function:
0
*
[0 - 1000 ] Indicates the number of fault events that have
occurred since last reset or power-up.
9-53 Profibus Warning Word
Range:
Function:
0
*
[0 -
65535 ]
This parameter shows PROFIBUS communication
warnings.
Bit
Description
0
Connection with DP master is lost.
1
Not used.
2
FDL (fieldbus data link layer) is not
OK.
3
Clear data command received.
4
Actual value is not updated.
5
Baud rate search.
6
PROFIBUS ASIC is not transmitting.
7
Initializing of PROFIBUS is not OK.
8
Frequency converter is tripped.
9
Internal CAN error.
10
Wrong configuration data from PLC.
11
Wrong ID sent by PLC.
12
Internal fault occurred.
13
Not configured.
14
Timeout active.
15
Warning 34 active.
Table 4.5 Bit Definition
9-63 Actual Baud Rate
Option:
Function:
This parameter shows the actual
PROFIBUS baud rate. The PROFIBUS
master automatically sets the baud
rate.
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255]
*
No baudrate found
9-64 Device Identification
Range:
Function:
0
*
[0 -
0 ]
NOTICE
This parameter is not visible via LCP.
The device identification parameter. The data type
is array[n] of unsigned16. The assignment of the 1st
subindexes is defined and shown in
Parameter Descriptions
VLT
®
Midi Drive FC 280
78