![Danfoss VLT Midi Drive FC 280 Programming Manual Download Page 67](http://html.mh-extra.com/html/danfoss/vlt-midi-drive-fc-280/vlt-midi-drive-fc-280_programming-manual_506511067.webp)
6-92 Terminal 42 Digital Output
Option:
Function:
Mode
is set to
[2] Position
Control
.
[171] Target Position Reached
The target position is reached.
This option is only effective
when
parameter 37-00 Application
Mode
is set to
[2] Position
Control
.
[172] Position Control Fault
A fault occurred in the
positioning process. Refer to
parameter 37-18 Pos. Ctrl Fault
Reason
for details about the
fault. This option is only
effective when
parameter 37-00 Application
Mode
is set to
[2] Position
Control
.
[173] Position Mech Brake
Selects mechanical control for
positioning. This option is only
effective when
parameter 37-00 Application
Mode
is set to
[2] Position
Control
.
[193] Sleep Mode
The frequency converter/system
has entered sleep mode. See
parameter group
22-4* Sleep
Mode
.
[194] Broken Belt Function
A broken-belt condition has
been detected. See parameter
group
22-4* Sleep Mode
.
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scale for the minimum output (0 mA or 4 mA)
of the analog signal at terminal 42. Set the
value to be the percentage of the full range of
the variable selected in
parameter 6-91 Terminal
42 Analog Output
.
6-94 Terminal 42 Output Max Scale
Range:
Function:
100
%
*
[0 -
200 %]
Scale for maximum output (20 mA) of the scaling
at terminal 42. Set the value to be the
percentage of the full range of the variable
selected in
parameter 6-91 Terminal 42 Analog
Output
.
(mA)
0%
20
0/4
100%
Current
Analog
output
Min Scale
par. 6-93
Variable
for
output
example:
Power
Analog
Output
Max Scale
par. 6-94
130BB772.10
Illustration 4.14 Output Scale versus Current
6-96 Terminal 42 Output Bus Control
Range:
Function:
0
*
[0 - 16384 ] Holds the analog output at terminal 42 if
controlled by bus.
6-98 Drive Type
Range:
Function:
0
*
[0 - 0 ]
Parameter Descriptions