14-65 Speed Derate Dead Time Compensation
Range:
Function:
Size
related
*
[ 20 -
1000 Hz]
Deadtime compensation level is reduced
linearly versus output frequency from
the maximum level set in
parameter 14-07 Dead Time Compen-
sation Level
to a minimum level set in
this parameter.
Selects the behavior when an option change is detected. This
parameter returns to
[0] Protect Option Config.
after an option
change.
Option:
Function:
[0]
*
Protect Option
Config.
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
[1]
Enable Option
Change
Settings can be changed when the
system configuration is being
modified.
14-90 Fault Level
Use this parameter to customize fault levels. Use the 8
th
element
to control the fault level of
alarm 13, Overcurrent
.
Option:
Function:
[3]
*
Trip Lock
Alarm is set to trip-lock.
[4]
Trip w.
delayed reset
Alarm is configured into trip alarm, which
can be reset after a delay time. For
example, if
alarm 13, Overcurrent
is
configured to this option, it can be reset 3
minutes after the alarm.
[5]
Flystart
At start-up, the frequency converter tries to
catch a spinning motor. If this option is
selected,
is
forced to
[1] Enabled
.
Index
Alarm
Trip lock
Trip w.
delayed
Flystart
0
Reserved
1
Reserved
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Reserved
7
Overcurrent
D
x
x
Table 4.6 Table for Selection of Action when
Selected Alarm Appears (
D=Default setting
x=Possible selection
Parameter Descriptions
VLT
®
Midi Drive FC 280