![background image](http://html.mh-extra.com/html/danfoss/vlt-midi-drive-fc-280/vlt-midi-drive-fc-280_programming-manual_506511009.webp)
1.3 Electrical Wiring - Control Cables
1.3.1 Overview
130BE202.12
3-phase
power
input
Switch mode
power supply
Motor
Analog output
interface
(PNP) = Source
(NPN) = Sink
ON = Terminated
OFF = Open
Brake
resistor
91 (L1)
92 (L2)
93 (L3)
PE
50 (+10 V OUT)
53 (A IN) **
54 (A IN)
55 (COM A IN)
0/4
−
20 mA
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
10 V DC
15 mA
100 mA
+
-
+
-
(U) 96
(V) 97
(W) 98
(PE) 99
(A OUT) 42
(P RS485) 68
(N RS485) 69
(COM RS485) 61
0 V
5 V
S801
0/4
−
20 mA
RS485
RS485
03
+10 V DC
0
−
10 V DC
24 V DC
02
01
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN)
0 V (PNP)
27 (D IN/OUT)
24 V
0 V
0 V (PNP)
24 V (NPN)
29 (D IN)
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
38 (D IN)****
37 (D IN)****
95
P 5-00
2
1
ON
(+DC/R+) 89
(-BR) 81
0
−
10 V DC
(-DC) 88
RFI
0 V
250 V AC, 3 A
Relay 1
*
***
Illustration 1.2 Basic Wiring Schematic Drawing
A=Analog, D=Digital
* Built-in brake chopper is only available on 3-phase units.
** Terminal 53 can also be used as digital input.
*** Switch S801 (bus terminal) can be used to enable termination on the RS485 port (terminals 68 and 69).
Introduction
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
7
1
1