To run AMA using the LCP
1.
By default parameter setting, connect terminals
12 and 27 before running AMA.
2.
Enter the
Main Menu
.
3.
Go to parameter group
1-** Load and Motor
.
4.
Press [OK].
5.
Set motor parameters using nameplate data for
parameter group
1-2* Motor Data
.
6.
Set motor cable length in
.
7.
Go to
parameter 1-29 Automatic Motor Adaptation
(AMA)
.
8.
Press [OK].
9.
Select
[1] Enable complete AMA
.
10.
Press [OK].
11.
The test runs automatically and indicates when it
is complete.
Depending on the power size, the AMA takes 3 to 10
minutes to complete.
NOTICE
The AMA function does not cause the motor to run and
it does not harm the motor.