16-22 Torque [%]
Range:
Function:
0 %
*
[ -200– 200 % ] View the torque in percent of nominal
torque, with sign, applied to the motor
shaft.
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 65535 V] View a measured value. The value is filtered
with a 30 ms time constant.
16-33 Brake Energy Average
Range:
Function:
0 kW
*
[0 - 10000
kW]
View the brake power transmitted to an
external brake resistor. The mean power is
calculated on an average level based on the
selected time period within
parameter 2-13 Brake Power Monitoring
.
16-34 Heatsink Temp.
Range:
Function:
0 °C
*
[-128 -
127 °C]
View the frequency converter heat sink
temperature. The cut-out limit is 90 ±5
°
C
[194
°
F], and the motor cuts back in at 60 ±5
°
C [140
°
F].
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 255 %] View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
Function:
0 A
*
[0 - 655.35 A] View the inverter nominal current, which
should match the nameplate data on the
connected motor. The data is used for
calculation of torque and motor protection.
16-37 Inv. Max. Current
Range:
Function:
0 A
*
[0 - 655.35 A] View the inverter maximum current, which
should match the nameplate data on the
connected motor. The data is used for
calculation of torque and motor protection.
16-38 SL Controller State
Range:
Function:
0
*
[0 - 20 ] View the state of the event under execution by
the SL controller.
16-39 Control Card Temp.
Range:
Function:
0 °C
*
[0 - 65535 °C] View the temperature on the control card,
stated in
°
C.
16-50 External Reference
Range:
Function:
0 %
*
[-200 -
200 %]
View the total reference, the sum of
digital, analog, preset, bus, and freeze
references, plus catch-up and slow-down.
16-52 Feedback[Unit]
Range:
Function:
0
ProcessCtrlUnit
*
[-4999 - 4999
ProcessCtrlUnit]
View the feedback unit
resulting from the selection
of unit and scaling in
,
parameter 3-01 Reference/
Feedback Unit
,
parameter 3-02 Minimum
Reference
, and
parameter 3-03 Maximum
Reference
.
16-53 Digi Pot Reference
Range:
Function:
0
*
[-200 -
200 ]
View the torque value with sign, applied to the
motor shaft. Some motors supply more than
160% torque. As a result, the minimum value
and the maximum value depend on the
maximum motor current as well as the motor
used.
16-57 Feedback [RPM]
Range:
Function:
0 RPM
*
[-30000 -
30000 RPM]
Readout parameter where the actual motor
RPM from the feedback source can be read
in both closed loop and open loop. The
feedback source is selected in
parameter 7-00 Speed PID Feedback Source
.
16-60 Digital Input
Range:
Function:
0
*
[0 -
65535 ]
View the actual state of the digital inputs 18, 19,
27, and 29.
Bit 0
Unused
Bit 1
Unused
Bit 2
Digital input terminal 29
Bit 3
Digital input terminal 27
Bit 4
Digital input terminal 19
Bit 5
Digital input terminal 18
Bit 6–15 Unused
Table 4.7 Bits Definition