1-82 Min Speed for Function at Stop [Hz]
Range:
Function:
0 Hz
*
[0 - 20 Hz] Set the output frequency at which to
activate
parameter 1-80 Function at Stop
.
1-83 Precise Stop Function
Option:
Function:
[0]
*
Precise ramp stop
[1]
Counter stop with reset
[2]
Counter stop without reset
[3]
Speed compensated stop
[4]
Speed compensated counter stop with reset
[5]
Speed compensated counter stop without reset
1-84 Precise Stop Counter Value
Range:
Function:
100000
*
[0 - 999999999 ]
1-85 Precise Stop Speed Compensation Delay
Range:
Function:
10 ms
*
[0 - 100 ms]
1-88 AC Brake Gain
Range:
Function:
1.4
*
[1.0 - 2.0 ]
1-90 Motor Thermal Protection
Option:
Function:
[0]
*
No
protection
Continuously overloaded motor, when no
warning or trip of the frequency converter is
required.
[1]
Thermistor
warning
Activates a warning when the connected
thermistor or KTY Sensor in the motor reacts
on a motor overtemperature.
[2]
Thermistor
trip
Stops (trips) the frequency converter when
the connected thermistor or KTY Sensor in
the motor reacts on a motor overtem-
perature.
The thermistor cut out value must be >3 k
Ω
.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3]
ETR warning
1
Calculates the load when set-up 1 is active,
and activates a warning in the display when
the motor is overloaded. Program a warning
signal via 1 of the digital outputs.
[4]
ETR trip 1
Calculates the load when set-up 1 is active,
and stops (trips) the frequency converter
when the motor is overloaded. Program a
warning signal via 1 of the digital outputs.
The signal appears in the event of a warning
and if the frequency converter trips (thermal
warning).
1-93 Thermistor Source
Option:
Function:
NOTICE
This parameter cannot be changed
while the motor is running.
NOTICE
Set the digital input to
[0] PNP - Active
at 24 V
in
parameter 5-00 Digital I/O
Mode
.
Select the input to which the thermistor (PTC
sensor) should be connected. An analog
input option
[1] Analog Input 53
or
[2] Analog
Input 54
cannot be selected if the analog
input is already in use as a reference source
(selected in
parameter 3-15 Reference 1 Source
parameter 3-16 Reference 2 Source
, or
parameter 3-17 Reference 3 Source
.
[0]
*
None
[1]
Analog
Input 53
[2]
Analog
Input 54
[3]
Digital input
18
[4]
Digital input
19
[5]
Digital input
32
[6]
Digital input
33