8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port and via 1 of the
digital inputs.
[3]
*
Logic OR
Activates the set-up selection via the fieldbus/
serial communication port or via 1 of the digital
inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
[0]
Digital
input
Activates preset reference selection via a digital
input.
[1]
Bus
Activates preset reference selection via the
serial communication port or fieldbus option.
[2]
Logic AND Activates preset reference selection via the
fieldbus/serial communication port and via 1 of
the digital inputs.
[3]
*
Logic OR
Activates the preset reference selection via the
fieldbus/serial communication port or via 1 of
the digital inputs.
8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[2]
Logic AND
[3]
*
Logic OR
8-79 Protocol Firmware version
Range:
Function:
Size related
*
[0 - 65535 ] Firmware revision: FC is in index 0;
Modbus is in index 1; indexes 2–4
are reserved.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of valid
telegrams detected on the bus.
8-81 Bus Error Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of telegrams
with faults (for example CRC faults) detected
on the bus.
8-82 Slave Messages Rcvd
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of valid
telegrams sent by the frequency converter to
the slave.
8-83 Slave Error Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of error
telegrams, which could not be executed by the
frequency converter.
8-84 Slave Messages Sent
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of messages
sent from the slave.
8-85 Slave Timeout Errors
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of slave
timeout errors.
8-88 Reset FC port Diagnostics
Option:
Function:
[0]
*
Do not reset
[1]
Reset counter
Parameter Descriptions
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
73