Troubleshooting by Remote Controller
Si37-701
224
Troubleshooting
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
Indoor Unit
A0
9
9
9
Error of external protection device
A1
9
9
9
PC board defect, E
2
PROM defect
A3
9
9
9
Malfunction of drain level control system (S1L)
A6
9
9
9
Fan motor (M1F) lock, overload
A7
8
7
9
Malfunction of swing flap motor (M1S)
A9
9
9
9
Malfunction of moving part of electronic expansion
valve / Dust clogging
AF
8
7
9
Drain level about limit
AH
8
7
9
Malfunction of air filter maintenance
—
AJ
9
9
9
Malfunction of capacity setting
C4
9
9
9
Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
C5
9
9
9
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
C9
9
9
9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
CJ
8
8
8
Malfunction of thermostat sensor in remote controller
Outdoor Unit
E1
9
9
9
PC board defect
E3
9
9
9
Actuation of high pressure switch
E4
9
9
9
Actuation of low pressure sensor
E5
9
9
9
Compressor motor lock
E6
9
9
9
Standard compressor lock or over current
E7
9
9
9
Malfunction of outdoor unit fan motor
E9
9
9
9
Malfunction of moving part of electronic expansion
valve (Y1E, Y2E, Y3E)
F3
9
9
9
Abnormal discharge pipe temperature
F6
9
9
9
Refrigerant overcharged
F9
9
9
9
Malfunction of BS unit electronic expansion valve
H7
9
9
9
Abnormal outdoor fan motor signal
H9
9
9
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
J2
9
9
9
Current sensor malfunction
J3
9
9
9
Malfunction of discharge pipe thermistor (R31, 32T,
33T) (loose connection, disconnection, short circuit,
failure)
J4
9
9
9
Malfunction of temperature sensor for heat
exchanger gas (R2T)
J5
9
9
9
Malfunction of thermistor (R8T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
J6
9
9
9
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
J7
9
9
9
Malfunction of receiver outlet liquid pipe thermistor (R6T),
(9T)
J8
9
9
9
Malfunction of liquid pipe thermistor 2 (R7T)
J9
9
9
9
Malfunction of subcooling heat exchanger gas pipe
thermistor (R5T)
JA
9
9
9
Malfunction of high pressure sensor
JC
9
9
9
Malfunction of low pressure sensor
L1
9
9
9
Malfunction of inverter PC board
L4
9
9
9
Malfunction of inverter radiating fin temperature rise
L5
9
9
9
DC output overcurrent of inverter compressor
L8
9
9
9
Inverter current abnormal
L9
9
9
9
Inverter start up error
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...