Si37-701
Specifications
Specifications
47
1.3
BS Units
Note:
★
1 When connecting with a 20 to 50 class indoor unit, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
★
2 When connecting with an indoor unit of 150 or more and 160 or less, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
★
3 When connecting with a 200 class, or more than 160 and less than 200 class indoor unit, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
Connection Range for BS Unit
Note:
★
Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% from single outdoor units, 160% from
double outdoor units, 130% from triple outdoor units.
Model
BSVQ100PV1
BSVQ160PV1
BSVQ250PV1
Power Supply
1 Phase 50Hz 200-240V
1 Phase 50Hz 200-240V
1 Phase 50Hz 200-240V
Total Capacity Index of Indoor Unit
20 to 100
More than 100 but 160 or less
More than 160 but 250 or less
No. of Connectable Indoor Units
Max. 5
Max. 8
Max. 5
Casing
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
Dimensions: (H×W×D)
mm
207×388×326
207×388×326
207×388×326
Sound Absorbing Thermal Insulation
Material
Foamed polyurethane, Flame resistant
needle felt
Foamed polyurethane, Flame resistant
needle felt
Foamed polyurethane, Flame resistant
needle felt
Piping
Connection
Indoor
Unit
Liquid Pipes
9.5mm C1220T (brazing connection)
★
1
9.5mm C1220T (brazing connection)
9.5mm C1220T (brazing connection)
Gas Pipes
15.9mm C1220T (brazing connection)
★
1
15.9mm C1220T (brazing connection)
★
2
22.2mm C1220T (brazing connection)
★
3
Outdoor
Unit
Liquid Pipes
9.5mm C1220T (brazing connection)
9.5mm C1220T (brazing connection)
9.5mm C1220T (brazing connection)
Suction Gas Pipes
15.9mm C1220T (brazing connection)
15.9mm C1220T (brazing connection)
★
2
22.2mm C1220T (brazing connection)
★
3
HP/LP Gas Pipes
12.7mm C1220T (brazing connection)
12.7mm C1220T (brazing connection)
★
2
19.1mm C1220T (brazing connection)
★
3
Weight
kg
14
14
15
Standard Accessories
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Drawing No.
C: 4D057926
C: 4D057927
C: 4D057928
REYQ16P
Same number of
BS units
REYQ18P
REYQ8P
REYQ10P
REYQ12P
REYQ14P
REYQ20P
REYQ22P
REYQ24P
REYQ26P
REYQ28P
REYQ30P
Indoor unit total capacity
Outdoor unit
model name
Total capacity of connectable indoor
units
Number of connectable
indoor units
Components
REYQ36P
REYQ38P
REYQ32P
REYQ34P
REYQ40P
REYQ42P
REYQ44P
REYQ46P
REYQ48P
100 to 260 (400)
125 to 325 (500)
150 to 390 (600)
175 to 455 (700)
200 to 520 (800)
225 to 585 (720)
250 to 650 (800)
275 to 715 (880)
300 to 780 (960)
325 to 845 (1,040)
350 to 910 (1,120)
375 to 975 (1,200)
400 to 1,040 (1,280)
425 to 1,105 (1,105)
450 to 1,170 (1,170)
475 to 1,235 (1,235)
500 to 1,300 (1,300)
525 to 1,365 (1,365)
550 to 1,430 (1,430)
575 to 1,495 (1,495)
600 to 1,560 (1,560)
13 (20)
16 (25)
19 (30)
22 (35)
26 (40)
29 (36)
32 (40)
35 (44)
39 (48)
42 (52)
45 (56)
48 (60)
52 (64)
55 (55)
58 (58)
61 (61)
64 (64)
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...