Si37-701
Outline of Control (Indoor Unit)
Function
141
6.4
Control of Electronic Expansion Valve
Electronic expansion valves in indoor units have the functions of conducting superheated
degree control in cooling operation and subcooled degree control in heating operation.
However, if the indoor units receive any control command such as a protection control
command or a special control command from the outdoor unit, the units will give a priority to the
control command.
• Superheated degree control in cooling operation
This function is used to adjust the opening of the electronic expansion valve so that
superheated degree (SH), which is calculated from the detection temperature (Tg) of the gas
pipe thermistor (R3T) and the detection temperature (T1) of the liquid temperature thermistor
(R2T) of the indoor unit, will come close to a target superheated degree (SHS).
At that time, correction to the superheated degree is made according to the differences (
∆
T)
between set temperature and suction air thermistor temperature.
• Normally 5°C.
• As
∆
T (Remote controller set temp. - Suction air temp.) becomes larger, SHS becomes
lower.
• As
∆
T (Remote controller set temp. - Suction air temp.) becomes samller, SHS
becomes higher.
• Sub cooled degree control in heating operation
This function is used to adjust the opening of the electronic expansion valve so that the high-
pressure equivalent saturated temperature (Tc), which is converted from the detected pressure
of the high pressure sensor in the outdoor unit, and the subcooled degree (SC), which is
calculated from the detected temperature (T1) of the liquid temperature thermistor (R2T) in the
indoor unit, will come close to the target subcooled degree (SCS).
At that time, corrections to the subcooled degree are made according to differences (
∆
T)
between set temperature and suction air thermistor temperatures.
• Normally 5°C.
• As
∆
T (Remote controller set temp. - Suction air temp.) becomes larger, SCS becomes
lower.
• As
∆
T (Remote controller set temp. - Suction air temp.) becomes lower, SCS becomes
larger.
SH = Tg - T1
SH:Evaporator outlet superheated degree (°C)
Tg:Indoor unit gas pipe temperature (R3T)
T1:Indoor unit liquid pipe temperature (R2T)
SHS (Target SH value)
SHS:Target superheated degree
SC = Tc - T1
SC:Condenser outlet subcooled degree (°C)
Tc:High pressure equivalent saturated temperature
detected by the high pressure sensor (S1NPH)
T1:Indoor unit liquid pipe temperature (R2T)
SCS (Target SC value)
SCS:Target supercooled degree
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...