Troubleshooting (OP: Unified ON/OFF Controller)
Si37-701
348
Troubleshooting
[CHECK 3] Check the Factors of Overheat Operation
Identify the defective points referring to the failure factor analysis (FTA) as follows.
Irregular piping length
Bend/collapse
(Including moisture choke)
Stop valve is closed.
4 way switch valve is in the
middle position.
Leak from hot gas bypass
valve
Subcooling
motor
operated
valve failure
Control
failure
Defective valve coil
Defective control PC board
Defective valve body
Defective valve coil
Defective valve body
Defective low pressure
sensor
Defective thermister for
suction pipe
Defective control PC board
Defective thermister for
indoor unit gas pipe
Defective thermister for
indoor unit liquid pipe
∗
1: Refer to “Low pressure protective control” (P126) for hot gas bypass control.
∗
2: Refer to P108 for subcooling electronic expansion valve control.
∗
∗
4: Superheating temperature control in heating mode is conducted by outdoor unit electronic expansion valve (EVM).
∗
5: Judgment criteria of superheat operation:
Suction gas superheating temperature: 10 degrees and over.
Discharge gas superheating temperature: 45 degrees
and over, except for immediately after starting and drooping control, etc..
(Use the above stated values as a guide. Depending on the other conditions, the unit may be normal despite the values
within the above scope.)
←
Check if coil resistance and insulation
are normal.
←
Check if coil resistance and
insulation are normal.
←
Check if the voltage property is
normal.
←
Check if the connector is connected properly.
Check if the thermister resistance property
is normal.
←
Check if the piping temperature connected
to the 4 way switch valve is normal.
←
Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.
←
Check if coil resistance and insulation are
normal.
←
Check if the connector is connected properly.
Check if the thermister resistance property is
normal.
←
Check if the connector is connected properly.
Check if the thermister resistance property is
normal.
←
Check if the connector is connected properly.
Check if the thermister resistance property is normal.
←
Check if coil resistance and insulation are
normal.
←
Check if the voltage property is normal.
←
Refer to [Check 7]
←
Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.
←
Does the piping length fall in the permissible range?
←
Corduet visual checks.
←
Remove the moisture by vacuum break. (Refer to [Check 8])
←
Check if the stop valve is open.
Faulty
discharge
pipe
temperature
control
Faulty hot
gas bypass
control
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective control PC board
Defective control
PC board
Defective valve coil
Defective low
pressure sensor
Defective subcool
heat exchange
outlet thermister
Defective valve
body
Faulty
subcooling
motorized
valve control
(EV2)
Superheat due to
shaft damage
Superheat due to
defective compressor
Indoor unit
motorized
valve failure
Faulty control
Faulty control
Outdoor unit
motorized
valve failure
Faulty of 4 way
switch valve
operation
[In cooling mode only]
(
∗
1)
(
∗
2)
Compressor
overheat
Refrigerant gas
shortage
Large resistance
of piping
Faulty
superheated
degree
control.
[In cooling mode]
When indoor unit
electronic
expansion valve
becomes too
narrow (
∗
3)
[In heading
mode]When
outdoor unit
electronic
expansion valve
becomes too
narrow (
∗
4)
Temperature
increase of
discharge
pipe
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...