Field Setting
Si37-701
208
Test Operation
3.2.10 Prevention of Small Heating in Non-operating Unit
In heating operation, this setting is made to prevent room temperature from rising due to small
heating capacity generated in the unit with its heating thermostat OFF or in the unit with its
heating operation stopped.
•
By switching the BS units to cooling when the system turns OFF the heating thermostat or
stops heating operation, small heating is prevented.
•
By enabling the small heating prevention setting of the outdoor unit, prevention of small
heating of all BS units connected to the outdoor unit is enabled. (Default setting of BS unit)
•
Setting by BS unit is enabled by changing the small heating prevention setting of every BS
unit. (In this case, enable the outdoor unit setting.)
3.2.11 Reduction of Cooling/Heating Selection Time of BS Units
Make this setting to reduce selection time between cooling and heating of the BS units, with
careful attention paid to the following points.
•
This setting is only enabled in case the refrigerant piping length between every BS unit
connected to the outdoor unit and the indoor unit is not more than 10 m. (Refer to the figure
shown below: (a)
≤
10 m and (b)+(c)
≤
10 m and
…
)
•
In case the refrigerant piping length between the BS units and the indoor units is long,
refrigerant passing sounds may become louder when the BS unit selects operation mode
between cooling and heating.
•
This setting reduces the operation mode selection time in all the BS units within the same
refrigerant circuit.
BS unit
Outdoor unit
a
Indoor unit
BS unit
b
Indoor unit
Indoor unit
c
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...