Si37-701
Test Operation
Test Operation
163
[Operation procedure]
To protect the compressor, make sure to turn on the power supply for 6 hours before stating
operation.
(After turning on the power supply, the unit can not start the operation until the H2P LED
goes off. (maximum 12 minutes))
Set to the SETTING MODE 1 (H1P : light OFF)
Push the TEST button (BS4) for 5 seconds or more. Then the unit will start the check
operation.
• The check operation is automatically carried out in a cooling mode. H2P will flash up
and "Test operation" and "Under centralized control" will be displayed in the remote
controller.
• It may take 10 minutes to bring the state of refrigerant uniform before the
compressor starts.
• During the check operation, the refrigerant running sound or the magnetic sound of
a solenoid valve may become loud during operation. And the LED display may
change, but these are not malfunctions.
• During the check operation, it is impossible to stop the unit from the remote
controller. When discontinue the operation, push the RETURN button (BS3). The
system will stop after behind operation for 30 seconds.
Close the front panel. (Otherwise, it may cause a misjudgment.)
When the checks are completed, the system will stop
automatically. After the system stopes the operation,
check the operation results by the outdoor unit LED
display. (See the table shown right.)
[Measure for abnormal finish]
Confirm the malfunction code by the remote controller, and correct the abnormality. (For how
to correct the abnormality, see the installation manual.)
After correcting the abnormality, push the RETURN button (BS3) and reset the malfunction
code.
Carry out the check operation again and confirm that the abnormality is properly corrected.
(
)
STATE
Normal
Abnormal
H1P H2P H3P H4P H5P H6P H7P
h
h
h
h
h
h
h
h
h
h
h
k
k
k
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...