Si37-701
Special Control
Function
111
3.
Special Control
3.1
Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
Actuator
Symbol
Elect.
symbol
Control
before
startup
Startup control
REYQ
REMQ
STEP1
STEP2
Compressor 1
—
M1C
M1C
0 Hz
52 Hz+OFF+OFF
52Hz+OFF+OFF+2STEP / 20
sec.
(Until it reaches
Pc-Pe>0.39 MPa)
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
STEP4
Ta<20°C: OFF
Ta
≥
20°C: STEP4
+1step/15 sec. (When
Pc_max>2.16 MPa)
-1step/15 sec. (When
Pc_max<1.77 MPa)
Outdoor unit fan 2
M2F
M2F
Electronic expansion
valve (Main)
EVM
Y1E
Y3E
Y1E
0 pls
1375 pls
1375 pls
Electronic expansion
valve (Supercooling)
EVT
Y2E
Y5E
Y3E
0 pls
0 pls
0 pls
Electronic expansion
valve (Refrigerant
charge)
EVJ
Y4E
Y2E
80 pls
80 pls
80 pls
Four way valve
(Heat exchanger switch)
20SA
Y2S
Y9S
Y3S
OFF
OFF
OFF
Four way valve (High/low
pressure gas pipe switch)
20SB
Y8S
Y2S
ON
ON
ON
Solenoid valve (Main
bypass)
SVE
Y5S
Y10S
Y6S
OFF
ON
ON
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
liquid pipe )
SVL
Y3S
Y4S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator gas
vent pipe)
SVG
Y1S
Y1S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
exhaust pipe)
SVO
Y7S
Y7S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVT
Y6S
Y8S
OFF
OFF
OFF
Ending conditions
A lapse of
60 sec.
A lapse of 15 sec.
•
A lapse of 90 sec.
•
Pc - Pe>0.39 MPa
OR
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...