Test Operation
Si37-701
158
Test Operation
1.2.5.2
Procedure of Adding Refrigerant Charging and Check Operation
Warning
Electric Shock Warning
Make sure to close the EL. COMPO. BOX lid before turning on the power when performing
the refrigerant charging operation.
Perform the setting on the PC board (A1P) of the outdoor unit and check the LED display
after the power is on via the inspection door which is in the EL. COMPO. BOX lid.
Use an insulated rod to operate the push buttons via the EL. COMPO. BOX’s inspection door.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.
Caution
Make sure to use the protect tool (protective groves and goggles) when charging the
refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be charged over the allowable
maximum amount when charging the refrigerant.
Do not perform the refrigerant charging operation under working for the BS and indoor unit.
When opening the front panel, make sure to take caution to the fan rotation during the
working.
After the outdoor unit stops operating, the fan may keep rotation for a while.
Note:
If operation is performed within 12 minutes after the BS, indoor and outdoor units are turned
on, H2P will be lit on and the compressor will not operate.
Check the LED display indicate as shown [Display of normal system] in chapter 1.2.5.2.1.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starting operating. This is not a malfunction.
The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the unit’s internal piping is already charged with
refrigerant, so be careful when connecting the charge hose.
After adding the refrigerant, make sure to close the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 Nm.
See [Shutoff valve operation procedure] in chapter 1.2.5.1 for details on how to handle
shutoff valves.
When done or when pausing the refrigerant charging operation, close the valve of the
refrigerant tank immediately.
The refrigerant charge port of this product have electric expansion valve.
The valve will be closed at end of refrigerant charging. However the valve will be opened on
operation after refrigerant charging (check operation, normal operation, etc.).
If the tank is left with the valve open, the amount of refrigerant which is properly charged
may be off the point.
Make sure to perform the check operation after installation. Otherwise, the malfunction code
“U3” will be displayed and normal operation cannot be performed.
And the failure of “Check of miswiring” may also cause abnormal operation. Performance
may drop due to the failure of “Judgment of piping length”.
Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.
The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is completed. (See
chapter 1.2.6)
The check operation cannot be performed in recovery or other service modes.
EL. COMPO. BOX
Inspection door
Inspection door
EL. COMPO. BOX lid
LED
(H1~8P)
Push button(BS1~5)
Lift the protruding part to
open the inspection door
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...