Si37-701
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
355
[Check 10] Check for causes of wet operation.
Referring to the Fault Tree Analysis (FTA) shown below, identify faulty points.
Refrigerant accumulation
Overcharge of refrigerant
Faulty crankcase heater
Frequent ON/OFF of compressor
[Cooling]
Indoor unit
motorized valve
opens too
much. (*1)
[Heating]
Outdoor unit
motorized valve
opens too
much. (*2)
Faulty control
of superheated
degree
Faulty indoor
unit motorized
valve
Faulty outdoor
unit motorized
valve
Faulty control
Faulty control
Faulty valve coil
Faulty control PC board
Faulty valve body
Faulty valve coil
Faulty valve body
Faulty power pressure sensor
Faulty suction pipe thermistor
Faulty control PC board
Faulty indoor unit
gas pipe thermistor
Faulty indoor unit
liquid pipe thermistor
←
Refer to information in the [Check 6]
section.
←
Does the valve coil have normal
resistance and insulation?
(Refer to information in the [Check 11]
section.)
←
Is the connector correctly connected?
Are the thermistor resistance
characteristics normal?
←
Is the connector correctly connected?
Are the thermistor resistance
characteristics normal?
←
Does the valve coil have normal
resistance and insulation?
(Refer to information in the [Check 11]
section.)
←
Are the voltage characteristics normal?
←
Is the connector correctly connected?
Does the thermistor have normal
resistance characteristics?
←
Is the pressure reading of the service
checker corresponding to the actual
measurement of the sensor?
←
Can the fan motor be rotated by
hand?
Does the fan motor coil have
normal resistance and
insulation?
←
Does the air filter get clogged?
←
Are there any obstacles in the air
passage?
Wet operation
Degraded
evaporation
capacity
Increased
resistance
in air
passage
Dirty evaporator
Reduced
air quantity
Reduced
fan output
*1: "Superheated degree control" in cooling operation is exercised with the indoor unit motorized valve. (Refer to
*2: "Superheated degree control" in heating operation is exercised with the outdoor unit motorized valve (EV1).
(Refer to information on P108.)
*3: Guideline of superheated degree to judge as wet operation
Suction gas superheated degree: Not more than 3
°
C;
Discharge gas superheated degree: Not more than
15
°
C, except immediately after compressor starts up or is running under drooping control.
(Use the values shown above as a guideline. Even if the superheated degree falls in the range, the compressor
may be normal depending on other conditions.)
Faulty fan motor
Dirty filter
Obstacles
Faulty control PC board
(including faulty
capacity setting)
←
Does the heat exchanger get clogged?
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...