Troubleshooting (OP: Unified ON/OFF Controller)
Si37-701
350
Troubleshooting
[CHECK 5] Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Short circuit
Rise in high
pressure
Local
pressure
rise
High pipe
resistance
Stop valve closed
Bent or crashed pipe
Clogging of foreign
particles
←
Check to be sure the stop valve is open.
←
Conduct visual checks for pipe conditions.
←
Is there any temperature difference caused before
and after the filter or branch pipe.
[In cooling]
If the outdoor unit electronic
expansion valve is throttled:
(See *1.)
Faulty outdoor
unit motorized
valve
Faulty valve coil
Faulty valve body
←
Are the coil resistance and insulation normal?
A temperature difference in excess of 10
°
C
between the inlet and the outlet is deemed to be abnormal.
Faulty
control
Faulty high pressure sensor
Faulty control PC board
←
Are the electrical characteristics normal?
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
←
Are the coil resistance and insulation
normal?
Faulty high
pressure
control
Faulty indoor
unit motorized
valve
Faulty valve coil
Faulty valve body
[In heating]
If the indoor unit electronic
expansion valve excessively
throttled:
(See *2.)
Faulty
control
Faulty high pressure sensor
Faulty indoor unit
liquid pipe thermistor
Faulty control PC board
←
Are the electrical characteristics normal?
←
In the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the pressure value checked with the Service
Checker corresponding to the measurement of the
pressure sensor?
[In cooling]
High suction
air
temperature
of the
condenser
[In heating]
High suction air
temperature
of outdoor unit
Short circuit
High ambient temperature
←
Is the suction air temperature not more than
43
°
C?
←
Is the outdoor temperature not more than 43
°
C?
High suction
air temperature
of indoor unit
High ambient temperature
←
Is the suction air temperature not more than 27
°
C?
←
Is the indoor temperature not more than 27
°
C?
Faulty suction air thermistor of indoor unit
High suction air temperature of outdoor unit
Faulty outdoor temperature thermistor of outdoor unit
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the outdoor temperature not more than 16
°
CWB?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation
in condensing
capacity
Dirty condenser
Mixing of non-condensable gas
←
Is the heat exchanger clogged? (In cooling)
←
Is air or else mixed in the refrigerant system?
Decreased
fan airflow
rate
Decreased
fan
output
Faulty fan
motor
←
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
←
If a spare PC board is mounted, is the
capacity setting properly made?
Faulty control
PC board
(Including
capacity setting)
High air
passage
resistance
Dirty filter
←
Is the air filter clogged?
Obstacle
←
Is there any obstacle in the air passage?
Excessive refrigerant charging
Improper model selection [In heating]
←
←
Is the indoor unit too small compared to
the large-sized outdoor unit?
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EVM) is fully open.
*2: In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(For details, refer to “Electronic Expansion Valve Control” on P141.)
SDK04009
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...