![Daikin VRV III REYQ8PY1 Service Manual Download Page 125](http://html1.mh-extra.com/html/daikin/vrv-iii-reyq8py1/vrv-iii-reyq8py1_service-manual_3513203125.webp)
Special Control
Si37-701
114
Function
3.3
Oil Return Operation
This function is used to recover refrigerant oil that flows out from the compressor to the system side by conducting oil
return operation in order to prevent the compressor from running out of refrigerant oil.
3.3.1 Cooling Oil Return Operation
[Start conditions]
Referring to the following conditions, start cooling oil return operation.
• Integral oil rise rate is reached to specified level.
• When cumulative compressor operating time exceeds 8 hours (2 hours when the power supply turns ON for
the first time)
Furthermore, the integral oil rise rate is calculated by Tc, Te, and compressor loads.
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the "Oil returning" process.
(Non-operating units stop while in "Preparation" mode.)
Outdoor unit actuator
Symbol
Elect. symbol
Oil return operation
Operation after oil return
REYQ REMQ
Compressor 1
—
M1C
M1C
52Hz+ON+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used
before oil return operation)
52Hz+ON+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used
before oil return operation)
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
Cooling fan control
Cooling fan control
Outdoor unit fan 2
M2F
M2F
Four way valve (for heat
exchanger selection)
20SA
Y2S
Y9S
Y3S
OFF
OFF
Four way valve (for high-
and low-pressure gas
pipe selection)
20SB
Y8S
Y2S
ON
ON
Electronic expansion
valve (main)
EVM
Y1E
Y3E
Y1E
1375pls
1375pls
Electronic expansion
valve (subcooling)
EVT
Y2E
Y5E
Y3E
SH control
SH control
Electronic expansion
valve (refilling refrigerant)
EVJ
Y4E
Y2E
80pls
80pls
Solenoid valve (main
bypass)
SVE
Y5S
Y10S
Y6S
ON
ON
Solenoid valve (hot gas)
SVP
Y4S
Y5S
OFF
OFF
Solenoid valve (liquid
pipe of refrigerant
regulator)
SVL
Y3S
Y4S
0pls
0pls
Solenoid valve (gas
discharge pipe of
refrigerant regulator)
SVG
Y1S
Y1S
0pls
0pls
Solenoid valve (drain pipe
of refrigerant regulator)
SVO
Y7S
Y7S
0pls
0pls
Solenoid valve (discharge
pipe of refrigerant
regulator)
SVT
Y6S
Y8S
0pls
0pls
End conditions
•
After a lapse of 5 min.
•
TsA - Te<5
°
C
•
After a lapse of 3 min.
•
Pe_min<5
°
C
•
Pc_max>3.63MPa
•
HTdmax>100
°
C
OR
or
or
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...