Field Setting
Si37-701
200
Test Operation
Setting of Demand Operation
By connecting the external contact input to the demand input of the outdoor unit external control
adaptor (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
A. When the demand operation is carried out by external instructions (with the use of the
external control adaptor for outdoor unit).
1. Connect the external adaptor of the outdoor unit, and then connect the external input wiring
to the low-noise operation input terminal on the terminal block (X1M). (Refer to the figure
shown below.)
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the Normal demand operation is carried out. (Use of the external control
adapter for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Description of setting
Setting procedure
Setting
item
Condition
Description
External control
adaptor
Outdoor unit PC board
Demand 1
Level 1
Operate with power
of approx. 60% or
less of the rating.
Short-circuit
between "1" and
"C" of the
terminal block
(TeS1).
Set the setting item No. 32 to
"Demand 1" and the setting item
No. 30 to "Level 1".
Level 2
Operate with power
of approx. 70% or
less of the rating.
Set the setting item No. 32 to
"Demand 1" and the setting item
No. 30 to "Level 2".
Level 3
Operate with power
of approx. 80% or
less of the rating.
Set the setting item No. 32 to
"Demand1" and the setting item
No. 30 to "Level 3".
Demand 2
–
Operate with power
of approx. 40% or
less of the rating.
Short-circuit
between "2" and
"C".
Set the setting item No. 32 to
"Demand 2".
Demand 3
–
Operate with forced
thermostat OFF
Short-circuit
between "3" and
"C"
–
To other external control adaptor
for outdoor unit
Demand
2
P
Outside
wiring
indicated by
dotted line.
3
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
F1
F2
N
1
C
Low
noise
X1M
Host computer monitor panel or demand controller
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...