Outline of Control (Indoor Unit)
Si37-701
138
Function
6.2.4 Thermostat Control with Operation Mode Set to "AUTO"
When the operation mode is set to "AUTO" on the remote controller, the system will conduct the
temperature control shown below.
Furthermore, setting changes of the differential value (D°C) can be made according to
information in the "Field settings with remote controller (p. 172 and later)" section.
: Factory setting
Mode
No.
Setting
switch No.
Contents of setting
Setting position No.
01
02
03
04
05
06
07
08
12
4
Differential value while in "AUTO"
operation mode
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C
Set heating temperature
(A-D)
°
C
Set cooling temperature
A
°
C
Display change
Cooling
→
Heating
Display change
Heating
→
Cooling
Cooling thermostat ON
Cooling thermostat OFF
Heating thermostat ON
Heating thermostat OFF
2
D
Differential value :0
°
C
27
°
C
25
°
C
30
°
C
Set cooling/
heating temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 1
°
C
26
°
C
24.5
°
C
29
°
C
Set heating temp.
27
°
C
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 2
°
C
24
°
C
28
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 3
°
C
23.5
°
C
Heating mode
Cooling mode
Control temp.
25
°
C
Set heating temp.
27
°
C
Set cooling temp.
24
°
C
Set heating temp.
27
°
C
Set cooling temp.
Differential value set to 4
°
C
26
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 5
°
C
22
°
C
22.5
°
C 25
°
C
Set heating temp.
27
°
C
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 6
°
C
22
°
C
24
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 7
°
C
21.5
°
C 23
°
C
Heating mode
Cooling mode
Control temp.
21
°
C
Set heating temp.
27
°
C
Set cooling temp.
20
°
C
Set heating temp.
27
°
C
Set cooling temp.
23
°
C
Set heating temp.
27
°
C
Set cooling temp.
(Ex.) When automatic cooling temperature is set to 27
°
C:
D
°
C
3
°
C
(
+2)
°
C
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...