Field Setting from Outdoor Unit
SiUS371901EB
229
Part 5 Field Settings and Test Operation
2.5 Monitoring Function and Field Settings
The operation of the outdoor unit can further be defined by changing some field settings. Next to
making field settings it is also possible to confirm the current operation parameters of the unit. The
setting can also be performed via the PC configuration software.
Below relevant Monitoring mode (mode 1) and Field setting mode (mode 2) settings are explained
in detail.
Making settings is done via the master outdoor unit.
2.5.1 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting contents
can be monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
shows whether the unit you are checking is a master or slave 1 unit.
No indication: undefined situation
0: outdoor unit is master unit
1: outdoor unit is slave 1 unit
Master and slave 1 indications are relevant in multiple outdoor unit system
configurations. The allocation of which outdoor unit is master and slave 1 are
decided by the unit’s logic.
The master unit must be used to input field settings in mode 2.
[1-1]:
shows the status of night-time low noise operation.
0: unit is currently not operating under low noise restrictions
1: unit is currently operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit
compared to nominal operating conditions.
Night-time low noise operation can be set in mode 2. There are two methods
to activate night-time low noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation by
field setting. The unit will operate at the selected low noise level during the
selected time frames.
The second method is to enable night-time low noise operation based on an
external input. For this operation an optional accessory is required.
[1-2]:
shows the status of power consumption limitation operation.
0: unit is currently not operating under power consumption limitations
1: unit is currently operating under power consumption limitation
Power consumption limitation reduces the power consumption of the unit compared
to nominal operating conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the outdoor unit
system.
The first method is to enable a forced power consumption limitation by field setting.
The unit will always operate at the selected power consumption limitation.
The second method is to enable power consumption limitation based on an external
input. For this operation an optional accessory is required.
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...