SiUS371901EB
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
234
78
Heat pump
lockout
temperature
Heat pump is locked out when the
outdoor air temperature is smaller
than the heat pump lockout
temperature.
2.
7
8
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
79
Heat pump
lockout release
differential
Heat pump would be resumed
when the outdoor air temperature
is recovered by differential above
the heat pump lockout
temperature.
2.
7
9
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
81
Cooling comfort
setting
Cooling comfort setting
2.
8
1
Eco
Mild
Quick
Powerful
0
1
2
3
82
Heating comfort
setting
Heating comfort setting
2.
8
2
Eco
Mild
Quick
Powerful
0
1
2
3
89
Intermittent fan
operation
Used for intermittent fan operation
setting
2.
8
9
OFF
30 minutes OFF, 1 minute ON
with medium fan speed
30 minutes OFF, 1 minute ON
with high fan speed
0
1
2
90
Indoor unit
without power
Multi-tenant function setting
2.
9
0
Invalid
Valid (No U4 error generation)
Valid (Operating with U4
warning)
0
1
2
92
Te target
temperature
upper limit
Used to make setting of targeted
evaporating temperature upper
limit for cooling and heat recovery
operation.
2.
9
2
L
M
H
0
1
2
97
Auxiliary heater
maximum
allowable
temperature
Auxiliary heater is allowed to
energize when the ambient
temperature is smaller than the
auxiliary heater maximum
allowable temperature.
2.
9
7
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
Auxiliary heater always not
allowed
Auxiliary heater always
allowed
1
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
98
Auxiliary heater
maximum
allowable
temperature
release
differential
Auxiliary heater is not allowed to
energize when the outdoor air
temperature is recovered by
differential above the auxiliary
heater maximum allowable
temperature.
2.
9
8
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...