Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
230
[1-5]:
shows the current Te target parameter position.
[1-6]:
shows the current Tc target parameter position.
[1-10]:
shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are
installed match the total number of indoor units which are recognized by the
system. In case there is a mismatch, it is advised to check the
communication wiring path between outdoor and indoor units (F1/F2
communication line).
[1-13]:
shows the total number of connected outdoor units.
It can be convenient to check if the total number of outdoor units which are installed
matches the total number of outdoor units which are recognized by the system. In
case there is a mismatch, It is advised to check the communication wiring path
between outdoor and outdoor units.
[1-17]:
shows the latest error code.
[1-18]:
shows the 2nd last error code.
[1-19]:
shows the 3rd last error code.
When the latest error codes were reset by accident on an indoor unit user interface,
they can be checked again through this monitoring settings.
[1-40]:
shows the current cooling comfort setting.
[1-41]:
shows the current heating comfort setting.
[1-42]:
shows the current high pressure sensor value (psi).
[1-43]:
shows the current low pressure sensor value (psi).
[1-44]:
shows the current compressor speed (Hz).
[1-45]:
shows the current EEV (heat exchanger upper) opening (pulse divided by 10).
[1-46]:
shows the current EEV (heat exchanger lower) opening (pulse divided by 10).
[1-47]:
shows the current discharge thermistor value (°F).
[1-49]:
shows the current compressor body thermistor value (°F).
[1-50]:
shows the current outdoor air thermistor value (°F).
[1-51]:
shows the current compressor suction thermistor value (°F).
[1-52]:
shows the current subcooling gas thermistor value (°F).
[1-53]:
shows the current heat exchanger gas (upper) thermistor value (°F).
[1-54]:
shows the current heat exchanger gas (lower) thermistor value (°F).
[1-55]:
shows the current deicer thermistor value (°F).
[1-56]:
shows the compressor run time (hour divided by 100).
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...