Troubleshooting by Error Code
SiUS371901EB
369
Part 6 Service Diagnosis
Note(s)
Reference
∗
1. REYQ-XATJU(A), REYQ-XAYDU(A): A3P
REYQ-XAYCU(A): A4P
CHECK 4
Refer to page 421.
CHECK 4
Is the power
transistor normal?
Power OFF
Power OFF
YES
YES
Restarting
the system results in
the recurrence
of the error.
Difference
between High
pressure and Low pressure
before the compressor
restart is below 0.2
MPa?
Continue operation.
Replace the
compressor.
Connect to power supply
within ±10% of the rated
voltage.
NO
NO
Pressure equalization
failure. Check the
refrigerant system.
Power
supply voltage
falls within ±10% of the
rated voltage?
YES
YES
Replace the inverter PCB. (*1)
Restarting
the system results
in the recurrence of the
error.
Continue operation.
The error could have
resulted from causes
such as instantaneous
power failure.
NO
NO
( )
A
YES
Replace the inverter PCB.
(*1)
NO
Power OFF
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...