SiUS371901EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
214
1.4.31 Drain Pump Operation Settings (for FXMQ-PB models)
The drain pump operation can be disabled for natural drainage by changing the following field
setting.
: Factory setting
1.4.32 Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20°C (68°F)
or above and turns OFF the humidifier if suction air temperature is 18°C (64.4°F) or below when the
heating thermostat is OFF.
: Factory setting
1.4.33 Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. If the second code is set to
02: Equipped, energy recovery ventilator fan conducts the fan residual operation by linking to
indoor unit. The indoor fan carries out residual operation for one minute after the thermostat is
stopped. (For the purpose of preventing dust on the air filter from falling off.)
: Factory setting
1.4.34 Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit,
this setting is unnecessary.
: Factory setting
1.4.35 Individual Setting of Ventilation
This is set to perform individual operation of Energy recovery ventilator using the remote
controller/central unit when Energy recovery ventilator is built in.
(Switch only when Energy recovery ventilator is built in.)
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
0
01
—
02
ON
03
OFF
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
1
01
Not equipped
02
Equipped
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
2
01
Not interlocked
02
Interlocked
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
5
01
— (Normal)
02
Individual
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...