Check
SiUS371901EB
443
Part 6 Service Diagnosis
Warning
Warning
Electrical Checks - High Voltage Power Circuits
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
Line Voltage now present.
7.
Depress the orange power button on the diagnostic tool to send a run signal to the motor.
Allow up to 5 seconds for the motor to start.
NOTE:
If the orange power button does not illuminate when depressed, the tool either
has an open fuse or is not properly connected to a 24VAC source.
8.
The green LED on the diagnostic tool will blink indicating communications between the
tool and motor. See table below for indications of tool indicators and motor actions.
Replace or repair as needed.
Power
Button
Green
LED
Motor
Action
Indication(s)
OFF
OFF
Not
Rotating
Confirm 24VAC to UltraCheck-EZ
TM
tool. If 24VAC
is confirmed, diagnostic tool is inoperable.
ON
Blinking
Rotating
Motor and control/end bell are functioning properly.
ON
OFF
Rotating
Replace motor control/end bell.
ON
Blinking
Not
Rotating
Check motor (refer to Motor Checks on page 445).
ON
OFF
Not
Rotating
Replace motor control/end bell; verify motor (refer to
Motor Checks on page 445).
9.
Depress the orange power button to turn off motor.
10. Disconnect power. Disconnect diagnostic tool.
11. Reconnect the 4-wire harness from control board to motor.
1.
Disconnect power to air handler or modular blower.
2.
Disconnect the 5-circuit power connector to the ECM motor.
3.
Turn on power to air handler or modular.
4.
Measure voltage between pins 4 and 5 on the 5-circuit connector. Measured voltage
should be the same as the supply voltage to the air handler or modular.
5.
Measure voltage between pins 4 and 3. Voltage should be approximately half of the
voltage measured in step 4.
1
2
3
4
5
Lines 1 and 2 will be connected
for 120VAC Power Connector
applications only
Gnd
AC Line Connection
AC Line Connection
}
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...