Field Settings for Indoor Unit
SiUS371901EB
207
Part 5 Field Settings and Test Operation
2. If the air passageway including duct or blow-off ports is changed after automatic adjustment,
make sure to perform automatic airflow adjustment again.
1.4.12 Compensating the Temperature around People (For units with the
infrared presence/floor sensor only)
Change the ratio between the suction air temperature and floor temperature used to calculate the
temperature around human.
The temperature around human is calculated using the values of the suction air thermistor and the
infrared floor sensor. The factory setting is Normal (the average value of the suction air temperature
and the floor temperature is applied). However, the rate at which the suction air thermistor and the
infrared floor sensor affect the temperature around human can be changed with this setting.
To reflect the effect of the temperature around the ceiling, select the "Priorities given on the
suction air temperature" (the Second code No.
02
).
To reflect the effect of the temperature around the floor, select the "Priorities given on the floor
temperature" (the Second code No.
04
).
The infrared presence/floor sensor can be disabled by selecting "Suction air temperature only"
(the Second code No.
01
).
: Factory setting
1.4.13 Compensating the Floor Temperature (For units with an infrared
presence/floor sensor only)
Offset the detected value of the infrared floor sensor with a certain temperature. This setting should
be used to have the actual floor temperature detected when, for example, the unit is installed close
to a wall.
: Factory setting
Actual procedure to use the setting
Although the standard setting is normally used with no problem, the setting should be changed in
the following cases:
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
8
01
Suction air temperature only
02
Priority given on the suction air temperature
03
Standard
04
Priority given on the floor temperature
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
9
01
–4°C (–7.2°F)
02
–2°C (–3.6°F)
03
0°C (0°F)
04
+2°C (+3.6°F)
Environment
Operation
Mode
Problem
Setting Value
- The unit is installed close to a wall or a window.
- High thermal capacity of the floor (such as
concrete, etc).
- There are many heat sources including PC.
- There is a non-negligible heat source such as
floor heating.
Heating
Excessive heating
+2°C (+3.6°F)
Insufficient
heating
–2°C or –4°C
(–3.6°F or –7.2°F)
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...