Field Setting from Outdoor Unit
SiUS371901EB
231
Part 5 Field Settings and Test Operation
2.5.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
0
COOL/HEAT
selection
Several systems as 1 zone
change over COOL/HEAT:
INDIVIDUAL: VRV indoor unit or
A-B-C input set mode.
MASTER: System is the
COOL/HEAT master unit.
SLAVE: System is not a
COOL/HEAT master.
2.
0
0
Individual
Unified Master
Unified slave
0
1
2
2
Low noise/
demand
address
Used to make address setting for
low noise/ demand operation.
2.
0
2
Address:
0
~
31
3
0
1
5
Indoor fan
forced H
Used to force the fan of indoor unit
to H tap.
2.
0
5
Normal operation
Indoor fan H
0
1
6
Forced
thermostat
Used to force all indoor units to
operate forced thermostat ON.
2.
0
6
Normal operation
Forced thermostat ON
0
1
8
Te setting
(Cooling
operation)
Used to make setting of targeted
evaporating temperature for
cooling operation.
2.
0
8
Auto
6°C (42.8°F)
7°C (44.6°F)
8°C(46.4°F)
9°C(48.2°F)
10°C (50.0°F)
11°C (51.8°F)
0
2
3
4
5
6
7
9
Tc setting
Used to make setting of targeted
condensing temperature for
heating
operation.
2.
0
9
Auto
41°C (105.8°F)
43°C (109.4°F)
46°C (114.8°F)
0
1
3
6
12
External low
noise setting/
demand setting
Used to receive external low noise
or
demand signal.
2.
1
2
Input LNO/DE
OFF
ON
0
1
13
AIRNET
address
Used to set address of AIRNET
2.
1
3
Address:
0
~
63
6
0
3
16 Heat pump
lockout 1
Used for heat pump lockout
2.
1
6
OFF
ON
0
1
18 High ESP
setting FAN
Fan high static pressure setting
2.
1
8
OFF
ON
0
1
20
Additional
refrigerant
charge
Used to perform additional
refrigerant charging operation
(compressor operation).
2.
2
0
Refrigerant charging
OFF
ON
0
1
21
Refrigerant
recovery and
vacuuming
Used to set the system to
refrigerant recovery mode (without
compressor run).
2.
2
1
Refrigerant recovery
OFF
ON
0
1
22
Automatic night-
time low noise
operation
Automatic night-time low noise
operation.
Time for the operation is subject to
the start and end time settings.
2.
2
2
OFF
Level 1
Level 2
Level 3
0
1
2
3
25
External low
noise level
Low noise level when the external
low noise signal is input at option
DTA104A61.
2.
2
5
Level 1
Level 2
Level 3
1
2
3
26
Automatic night-
time low noise
operation start
Time to start automatic “night-time
low noise” operation. (“Night-time
low noise” level setting should also
be made.)
2.
2
6
About 8:00 PM
About 10:00 PM
About 12:00 AM
1
2
3
27
Automatic night-
time low noise
operation stop
Time to stop automatic “night-time
low noise” operation. (“Night-time
low noise” level setting should also
be made.)
2.
2
7
About 6:00 AM
About 7:00 AM
About 8:00 AM
1
2
3
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...