SiUS371901EB
Outline of Control (Indoor Unit)
Part 4 Functions and Control
174
Note(s)
When the indoor unit is FXFQ-T, FXZQ-TA or FXUQ-P, if the air outlet is set as dual-directional or
tri-directional, the starting conditions will be changed as follows.
Liquid pipe temperature
≤
1°C (33.8°F) (for total of 15 minutes)
or
Liquid pipe temperature
≤
0°C (32°F) (for 1 minute continuously)
During freeze-up prevention control, the airflow rate is fixed to LL.
(The cancelling conditions are same as the standard.)
0
ºC
(32˚F)
+
7
ºC
(44.6˚F)
10 min.
1 min.
+
1
ºC
(33.
8
˚F)
t1
t2
t3
t4
+
7
ºC
(44.6˚F)
10 min.
OR
t
>
15
min
u
tes
Freeze-
u
p pre
v
ention control
Forced OFF
b
y thermostat
Freeze-
u
p pre
v
ention control
Forced OFF
b
y thermostat
Li
qu
id pipe
temperat
u
re
Start
Cancel
Start
Cancel
N
ormal operation
N
ormal operation
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...