Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
244
Note(s)
∗
1. Indoor condition A: Temperature difference Average of (indoor air temperature – set
temperature) is less than 1.5°C (2.7°F).
∗
2. Indoor condition B: Temperature difference Average of (indoor air temperature – set
temperature) is 3°C (5.4°F) or more.
[2-35]:
Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed
on a higher position than outdoor units) and the height difference between the
highest indoor unit and the outdoor unit exceeds 40 m (130 ft), the setting [2-35]
should be changed to 0.
[2-38]:
Emergency operation “Master”
To disable permanent compressor operation: in case of single module or “Master”
unit of a multi outdoor system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 3: master module is disabled permanently.
[2-39]:
Emergency operation “Slave 1”
To disable permanent compressor operation of “Slave 1” unit of a multi outdoor
system: Default value: 0. Compressor operation enabled.
Field setting:
Set 3: Slave 1 module is disabled permanently.
[2-40]:
Emergency operation “Slave 2”
To disable permanent compressor operation of “Slave 2” unit of a multi outdoor
system: Default value: 0. Compressor operation enabled.
Field setting:
Set 3: Slave 2 module is disabled permanently.
Combination table setting 2-38, 2-39 and 2-40:
Disable
Master/
individual
Slave 1
Slave 2
Module
2-38-3
2-39-3
2-40-3
[2-42]:
Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise
between outdoor units.
Default value: 0
Field setting:
Mode A: 1
Mode B: 2
[2-45]:
Low ambient cooling
Default value: 0.
[2-45]
Description
0 (default)
No low ambient cooling available.
1
Low ambient cooling available.
This setting is not applicable to Multi Branch Selector unit (standard series).
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...