Field Setting from Outdoor Unit
SiUS371901EB
233
Part 5 Field Settings and Test Operation
35
Outdoor > 40 m
(130 ft) below
indoor
To increase Tc target heating.
2.
3
5
Level > 40 m (130 ft)
Level max. 40 m (130 ft)
Do not use
0
1
~
7
37
Heat pump
lockout 2
Used for heat pump lockout
2.
3
7
OFF
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
0
1
2
3
4
5
6
38
Emergency
operation
(master)
To prohibit a compressor or
complete in “Master”. Since
module is permanent disabled,
immediately replace the defective
component(s).
2.
3
8
OFF
Master unit OFF
0
3
39
Emergency
operation (slave
1)
To prohibit a compressor or
complete “Slave 1”. Since module
is permanent disabled,
immediately replace the defective
component(s).
2.
3
9
OFF
Slave 1 unit OFF
0
3
40
Emergency
operation (slave
2)
To prohibit a compressor or
complete “Slave 2”. Since module
is permanent disabled,
immediately replace the defective
component(s).
2.
4
0
OFF
Slave 2 unit OFF
0
3
42
Outdoor fan
Outdoor fan noise
countermeasure (limit fan speed).
2.
4
2
Standard
Mode A
Mode B
0
1
2
45
Low ambient
cooling
Low ambient cooling function
setting.
This setting is not applicable to
Multi Branch Selector unit
(standard series).
2.
4
5
Low ambient cooling not
available
Low ambient cooling
available
0
1
47
Te setting (Heat
recovery
operation)
Used to make setting of targeted
evaporating temperature for heat
recovery operation.
2.
4
7
Auto
6°C (42.8°F)
7°C (44.6°F)
8°C (46.4°F)
9°C (48.2°F)
10°C (50.0°F)
11°C (51.8°F)
0
2
3
4
5
6
7
49
Outdoor > 50 m
(164 ft) above
indoor
Height difference setting max. 90
m (295 ft).
2.
4
9
Off (max. 50 m (164 ft))
On (max 90 m (295 ft))
0
1
51
Sequence multi
outdoor
Sequence addressing between
master and slave units.
2.
5
1
Automatic
Forced master
Forded slave 1
Forced slave 2
0
1
2
3
60
Gas furnace
setting
Used for gas furnace connection
2.
6
0
No gas furnace connection
Gas furnace connection
0
1
62
Cooling/Heating
capacity
learning control
Adjust cooling and heating
capacity learning control
2.
6
2
OFF
Cooling adjustment
Heating adjustment
Cooling and heating
adjustment
0
1
2
3
71
Branch selector
switching time
Used for changing branch selector
switching time
All piping length between branch
selector
unit and indoor units should be
less than 9.7 m (32 ft).
2.
7
1
Standard
Approximately 4 minutes
0
1
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...