Field Settings for Indoor Unit
SiUS371901EB
219
Part 5 Field Settings and Test Operation
1.6 List of Field Settings for Outdoor-Air Processing Unit
: Factory setting
1.7 Setting of Operation Control Mode
The operation control mode is compatible with a variety of controls and operations by limiting the
functions of the operation remote controller. Furthermore, operations such as remote controller
ON/OFF can be limited in accordance with the combination conditions. (Refer to information on the
next page.)
Central remote controller is normally available for operations. (Except when centralized monitor is
connected)
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only. (Cannot be turned
ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller
only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by
remote controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.
Whether operation by remote controller will be possible or not for turning ON/OFF, controlling
temperature or setting operation mode is selected and decided by the operation mode given on the
right edge of the table below.
Mode
No.
First
Code
No
Setting Contents
Second Code No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
10
(20)
0
Filter contamination
2500 hr
1250 hr
—
—
—
—
—
—
—
—
—
—
—
—
—
3
Display time to clean
air filter calculation
Display
No
display
—
—
—
—
—
—
—
—
—
—
—
—
—
12
(22)
1
External ON/OFF
input
Forced
OFF
ON/OFF
control
—
—
—
—
—
—
—
—
—
—
—
—
—
5
Power failure
automatic reset
Not
equipped
Equipped
—
—
—
—
—
—
—
—
—
—
—
—
—
14
(24)
3
Discharge pipe
temperature
(cooling)
°C
13
14
15
16
17
18
19
20
21
22
23
24
25
°F
55.4
57.2
59 60.8 62.6
64.4
66.2 68 69.8 71.6 73.4 75.2
77
4
Discharge pipe
temperature
(heating)
°C
18
19
20
21
22
23
24
25
26
27
28
29
30
°F
64.4
66.2
68 69.8 71.6 73.4 75.2
77
78.8 80.6 82.4 84.2
86
Contents of Control Modes
How to Select Operation Mode
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...