Field Setting from Outdoor Unit
SiUS371901EB
253
Part 5 Field Settings and Test Operation
2.7 Night-Time Low Noise Operation and Demand Operation
2.7.1 Night-Time Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external control
adaptor (optional), you can lower operating noise.
Setting
Content
Level 1
Set the outdoor fan to Step 6 or lower.
Level 2
Set the outdoor fan to Step 5 or lower.
Level 3
Set the outdoor fan to Step 4 or lower.
A.
1.
When night-time low noise operation is carried out by external contact (with
the use of the external control adaptor for outdoor unit).
Connect external control adaptor for outdoor unit and short circuit terminal of
night-time low noise operation (Refer below figure). If carrying out demand or low
noise input, connect the adaptor’s terminals as shown below.
2.
3.
4.
While in setting mode 2, set the item 2-12 (External low noise or demand setting)
to ON.
If necessary, while in setting mode 2, select an external low noise level for the item
2-25.
If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to
ON. (If the condition is set to ON, when the air conditioning load reaches a high
level, the low noise operation command will be ignored to put the system into
normal operation mode.)
B.
1.
2
3.
4.
When night-time low noise operation is carried out automatically. (External
control adaptor for outdoor unit is not required.)
While in setting mode 2, select a night-time low noise operation level for the item
2-22.
If necessary, while in setting mode 2, select a starting time of night-time low noise
operation (i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the
starting time as a guide since it is estimated according to outdoor temperatures.)
If necessary, while in setting mode 2, select an ending time of night-time low noise
operation (i.e., 6:00 AM, 7:00 AM, or 8:00 AM) for the item 2-27. (Use the ending
time as a guide since it is estimated according to outdoor air temperatures.)
If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to
ON. (If the condition is set to ON, when the air conditioning load reaches a high
level, the system will be put into normal operation mode even during night-time.)
O
u
tdoor
w
iring indicated
b
y dotted line
External control
adaptor for
o
u
tdoor
u
nit
Host comp
u
ter
monitor panel
or demand
controller
X
X
X
X
F1
F2
P3
P4
F1
F2
P3
P4
X
X
X
X
X
X
1
2
3
C
Demand
Lo
w
noise
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...