4
Set-up and installation
Installation and operating instructions
14
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
▪ The cross-section of this installation shaft must be sized so that
between the external wall of the flue gas line
and the
internal
face of the installation shaft
the following
minimum distance
must be maintained:
▪ with a rectangular shaft cross-section:
2 cm
▪ with a round shaft cross-section:
3 cm
B
23
:
▪ Flue gas pipe without flow safeguard - vacuum operation
▪ Properties and application options of the flue gas pipe:
▪ Minimum requirements according to
Chap. 4.5.1
fulfilled.
▪ Opening for flue gas outlet to the outside
▪ Supply air directly from installation room (see
Chap. 4.2.3
).
▪ If the dimensions of the flue gas line differ from those described in
this manual, a suitable arithmetical dimensioning verification is re-
quired.
▪ For data on dimensioning, see
Chap. 14.1
.
B
23P
:
▪ as for B
23
, but underpressure operation
B
33
:
▪ Connection of more than one device to a common flue gas system
(vacuum flue gas shaft).
▪ Vertical opening for flue gas outlet.
▪ Supply air directly from installation room (see
Chap. 4.2.3
).
▪ Suitable arithmetical dimensioning verification required because
vacuum prevails in the case of the flue gas inlet into the common
air/flue gas system.
▪ For data on dimensioning, see
Chap. 14.1
.
▪ Parts under overpressure of the connection pipe must be conduc-
ted as a concentric pipe system.
B
53
:
▪ as for B
33
, but connection to associated flue gas pipe including flue
gas opening.
B
53P
:
▪ as for B
53
, but overpressure operation.
Spacings of brackets and offsets
The distance of the supports of the flue gas line must not be more
than 2 m in the vertical area.
In the horizontal area of the connecting lines, the brackets must be
installed so tightly that there is no risk of any gradient in the hori-
zontal area in which condensate could accumulate.
If an offset is required in the vertical part of the flue gas line, the
maximum angle must not exceed 45°. In the case of external install-
ation, the height above the last bracket must not exceed 1.5 m.
4.3
Transport and delivery
WARNING
Lifting or displacing the A2 F by the panels can damage
the device.
▪ Only carry the A2 F with the cover removed, in pairs us-
ing the recessed grips provided for this purpose in the
rear panel of the device and on the boiler frame.
The A2 F is delivered on a pallet. All industrial trucks, such as lifting
trucks and forklift trucks, are suitable for transporting it.
Scope of delivery
▪ A2 F (preassembled),
▪ Boiler cladding (see
Fig. 4-3
)
▪ Screws for boiler cladding
▪ Documentation package
▪ Cable tie
▪ oil filter
▪ External temperature sensor
Fig. 4-3
Scope of delivery standard accessories package
Item
Designation
A
Boiler cladding – side panel
B
Boiler cladding – side panel
C
Boiler cladding – cover
D
Boiler cladding – front panel
E
Small accessories: Screws, 4-pin circuit board con-
nector, strain relief clip (3x)
F
Cable tie
G
External temperature sensor
H
oil filter
I
Documentation
Tab. 4-3
Legend for
Fig. 4-3
For A2 F accessories, see price list.