12
Technical data
Installation and operating instructions
59
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
12.2
Flow rate and residual feed height
Fig. 12-2
Residual feed height A2 F (heating side)
Item
Designation
Δ
p
R
Remaining feed height
m
H
Heating network flow rate
1
Modulation range
Tab. 12-11 Legend for
Fig. 12-2
Fig. 12-3
Required flow rates depending on the heating output
and the dimensioned temperature spread
Item
Designation
m
H
Heating network flow rate
Q
Heating output
S
Spread
Tab. 12-12 Legend for
Fig. 12-3
12.3
Temperature sensor
Fig. 12-4
Resistance characteristics of the temperature sensor
Item
Designation
R
S
Sensor resistance
T
Temperature
Tab. 12-13 Legend for
Fig. 12-4
Measured
temperature
in °C
Temperature sensor
Type
Specification *
NCT
t
V1
, t
R
, t
V2
, t
AU
, t
DHW
, t
Mi
PT1000,
t
AG
Sensor resistance in Ohm according to standard
or manufacturer's data
-20
98660
922
-10
56250
961
0
33210
1000
10
20240
1039
20
12710
1077
30
8195
1116
40
5416
1155
50
3663
1194
60
2530
1232
70
1782
1270
80
1278
1308
90
932
1347
100
690
1385
110
519
1423
120
395
1461
Tab. 12-14 Resistance values of the temperature sensor