12
Technical data
Installation and operating instructions
55
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
12
Technical data
12.1
Basic data
Boiler type
A2 F 18H
A2 F 24H
A2 F 32H
Parameters
Unit
Product Identification Number (CE number)
CE 0085 …..
Length
mm
754
Width
mm
606
Height
mm
1360
Weight of the boiler body
kg
63
68
77
Complete weight (empty – without condensate
box)
kg
97
102
111
Transport weight unit (without condensate box)
kg
109
114
123
Water content
l
60
56
50
Nominal heat output P
n
(80/60 °C as per EN 303)
kW
8.3 – 17.7
10.6 – 24.1
12.5 – 31.4
Nominal heat output in condensation mode P
c
(50/30 °C as per EN 15034)
kW
Maximum permissible inflow temperature
°C
85
Maximum permitted operating overpressure
PMS
bar
3
CO emission class (as per EN 267)
3
3
3
NO
X
emission class (as per EN 267)
3
3
3
Diameter of flue gas connection/supply air con-
nection
mm
80 / 125
Voltage
V
~230
Power supply frequency
Hz
50
Max. electric power consumption (without/with
circulation pump)
W
184 / 242
204 / 264
228 / 289
Max. electric power consumption in "Standby"
operating mode
W
3.4
Protection type
IP X0B
Tab. 12-1
Basic data A2 F
Boiler type
A2 F 18H
A2 F 24H
A2 F 32H
Burner type
HLM 35 AV 16 G1 G1
HLM 35 AV 19 G1 G1
HLM 35 AV 21 G1 G1
Parameters
Unit
Furnace thermal capacity Q
n
kW
8.5 – 18.2
10.9 – 24.7
12.8 – 32.2
Oil throughput
kg/h
0.72 – 1.53
0.92 – 2.08
1.08 – 2.72
Heating oil
EL as per DIN 51603-1 (max. sulphur content 0.1%), preferably low-sulphur
Maximum bio-heating oil content
%
10 (BTL or FAME as per DIN V 51603-6)
Hydraulic system
Modulating with oil preheating
Air regulation
Speed-controlled blower
Weight
kg
9
Test as specified in EN 267
Voltage
V
~230
Power supply frequency
Hz
50
Tab. 12-2
Basic data oil burner