ENGLISH
114
7.2
Manual reset of error conditions
In error status, the user can reset the fault by overriding a new attempt by pressing and releasing b and -.
7.3
Auto-reset of error conditions
In the cases of some malfunctions and block conditions, the system makes a number of attempts at automatic reset of the electric
pump. The auto-reset system regards in particular:
-
"BL"
Block due to water failure
-
"LP"
Block due to low power supply voltage
-
"HP"
Block due to internal high voltage
-
"OT"
Block due to overheating of final power stages
-
"OB"
Block due to overheating of printed circuit
-
"OC"
Block due to current overload on electric pump motor
-
"OF"
Block due to current overload on final stages of output
-
"BP"
Block due to fault on pressure sensor
If, for example, the pump is blocked due to water supply failure, the inverter automatically starts a test procedure to verify that the
unit is effectively without water permanently. During the sequence of operations, if a reset attempt succeeds (for example water has
returned), the procedure is interrupted and normal operation is resumed.
Table 31 shows the sequence of operations performed by the inverter for the different types of block.
Automatic reset of error conditions
Display message
Description
Automatic reset sequence
BL
Block due to water failure
- One attempt every 10 minutes for a total of 6 attempts
- One attempt every hour for a total of 24 attempts
- One attempt every 24 hours for a total of 30 attempts
LP
Block due to low line voltage
- Reset when specified voltage is restored
HP
Block due to high internal power
supply voltage
- Reset when voltage returns to a specified value
OT
Block due to overheating of final
power stages
(TE > 100°C)
- Reset when temperature of final power stages falls below 85°C
OB
Block due to overheating of printed
circuit
(BT> 120°C)
- Reset when temperature of printed circuit falls below 100°C
OC
Block due to current overload on
electric pump motor
-
An attempt every 10 minutes for a total of 6 attempts
-
An attempt every hour for a total of 24 attempts
-
An attempt every 24 hours for a total of 30 attempts
OF
Block due to current overload on
final stages of output
-
An attempt every 10 minutes for a total of 6 attempts
-
An attempt every hour for a total of 24 attempts
-
- An attempt every 24 hours for a total of 30 attempts
Table 31: Auto-reset of blocks
Summary of Contents for PWM 203
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...