ENGLISH
105
To help the user with the setting, the page shows the dry running factor measured in real time (in addition to the SO minimum dry
running factor to be set). The value measured is shown in a box below the name of the SO parameter and is called “SOm”.
In the multi inverter configuration, SO is a parameter which can be propagated between inverters but it is not a sensitive
parameter, i.e. it does not necessarily have to be the same for all inverters. When a change in SO is measured the user is asked
whether the value should be propagated to all the inverters.
6.5.15
MP: Minimum pressure pump stop due to water failure
This sets the minimum pressure pump stop due to water failure. If the system pressure reaches a pressure below MP the lack of
water is signalled.
This parameter is set on all systems without flow sensor. If the pump functions with flow sensor MP is blocked and disabled.
The MP default value is 0.0 bar and can be set up to 5.0 bar.
If MP=0 (default), the dry running is detected by the flow or the dry running factor SO algorithm;
if MP is not equal to 0, the lack of water is detected when the pressure is below the MP value.
The lack of water alarm is detected only when the pressure goes below the MP value for the amount of time set for the TB value, see
par. 6.6.1.
In the multi inverter configuration, MP is a sensitive parameter therefore it must always be the same along the chain of inverters in
communication and when the value is changed it is automatically propagated to all the inverters.
6.6
Technical Assistance Menu
From the main menu, press and hold “MODE” & “SET” & “+“ simultaneously until “TB” appears on display (or use the b or –
in the selection menu). This menu enables the display and modification of various configuration parameters. The MODE button
enables the user to scroll through the menu pages, while b and – enable respectively to increase and decrease the value of
the parameter concerned. To exit the current menu and return to the main menu, press SET.
6.6.1
TB: Water failure block time
Entry of a water failure block delay time enables selection of the time (in seconds) taken by the inverter to notify of low water levels
on the electric pump.
Modifications to this parameter may be useful if a known delay exists between the moment in which the pump is activated and the
actual moment of supply. One example is that of a system where the electric pump intake line is particularly long and is subject to
small leaks. In this case it may occur that the pipeline empties, and even if the water supply is regular, the electric pump takes some
time to reload, deliver flow and pressurise the system.
6.6.2
T1: Shutdown time after low pressure signal
This sets the inverter shutdown time starting from reception of the low pressure signal (see Impostazione della rilevazione di bassa
pressione par 6.6.13.5). The low pressure signal may be received on any of the 4 inputs, by suitably configuring the input (Setup
degli ingressi digitali ausiliari IN1, IN2, IN3, IN4 par 6.6.13).
T1 can be set between 0 and 12 s. The default setting is 2 s.
6.6.3
T2: Shutdown delay
This sets the delay after which the inverter shuts down after shutdown conditions have been reached: system pressure and flow at
minimum values.
T2 can be set between 5 and 120 s. The default setting is 10 s.
6.6.4
GP: Proportional gain coefficient
The proportional gain should generally be increased for elastic systems (wide and PVC pipelines) and reduced in the case of rigid
systems (narrow and steel pipelines).
To maintain constant system pressure, the inverter performs a PI check on the measured pressure error. On the basis of this error,
the inverter calculates the power to supply to the electric pump. The behaviour of this check depends on the set parameters GP and
GI. To meet the different requirements of the various types of hydraulic systems where the system may operate, the inverter enables
the selection of parameters that are different from the default settings.
On virtually all systems, the factory setting of parameters
GP and GI are optimal.
However, in the event of problems with regulation, these settings may be modified as required.
Summary of Contents for PWM 203
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...