ENGLISH
98
During normal operation, the system pressure is set at 3.0 [bar].
The electric pump is restarted when the pressure falls below 2.5 [bar].
Entry of an excessively high pressure setting (SP, P1, P2, P3, P4) with respect to the pump output specifications, may
cause false errors of water failure (BL); in this case lower the pressure setting or use a pump suited to system
requirements.
6.4
Manual menu
From the main menu, press and hold “SET" & “+” & “-“ simultaneously until “FP” appears on display (or use the b or – in the
selection menu).
This menu enables the display and modification of various configuration parameters. The MODE button enables the user to scroll
through the menu pages, while b and – enable respectively to increase and decrease the value of the parameter concerned.
To exit the current menu and return to the main menu, press SET.
In manual mode, regardless of the parameter on display, the following commands are enabled
:
Temporary start-up of electric pump
When the buttons MODE and - are pressed simultaneously, the pump is started up at the frequency FP and this operating status
remains while the buttons are pressed.
When the pump ON or pump OFF command is activated, the relative notification is shown on display.
Pump start-up
When the buttons MODE and + are pressed simultaneously for 2 seconds, the pump is started up at the frequency FP. This
operating status remains until SET is pressed. When SET is pressed again, the user exits the manual mode menu.
When the pump ON or pump OFF command is activated, the relative notification is shown on display.
Inversion of direction of rotation
When the buttons SET and - are pressed simultaneously for 2 seconds, the pump changes direction of rotation. The function is also
enabled when the motor is running.
6.4.1
FP: Test frequency setting
This displays the test frequency in [Hz] and enables modification by means of the buttons “+” and “-“.
The default value is FN – 20% and can be set between 0 and FN.
6.4.2
VP: Display of pressure
System pressure measured in [bar] or [psi] depending on measurement system selected.
6.4.3
C1: Display of phase current
Phase current of electric pump in [A]
A round flashing symbol may appear under the phase current C1 symbol. This signals that the pre-alarm threshold of maximum
current allowed has been exceeded. If the symbol flashes at regular intervals it means that the motor overcurrent protection is being
activated and that it will probably be triggered. In this case it is necessary to check the correct setting of the maximum current of the
RC pump, see paragraph 6.5.1 and the electric pump connections.
6.4.4
PO: Display of the power delivered
Power delivered to the electric pump in [kW].
A round flashing symbol may appear under the measured power PO symbol. This signals that the pre-alarm threshold of maximum
power allowed has been exceeded.
6.4.5
RT: Setting the direction of rotation
If the direction of pump rotation is incorrect, it can be inverted by changing this parameter. In this menu item, use b and – to
activate and display the two possible states “0” or “1”. The phase sequence is shown in the comment line on display. The function is
also enabled when the motor is running.
Summary of Contents for PWM 203
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...