ENGLISH
113
Alarm in fault log
Display message
Description
PD
Irregular shutdown
FA
Problems with cooling system
Table 29: Alarms
Block conditions
Display message
Description
BL
Block due to water failure
BPx
Block due to reading error of the pressure sensor named
LP
Block due to low power supply voltage
HP
Block due to high internal power supply voltage
OT
Block due to overheating of final power stages
OB
Block due to overheating of printed circuit
OC
Block due to current overload on electric pump motor
OF
Block due to current overload on final stages of output
SC
Block due to direct short circuit between the phases on the output terminal
EC
Block due to lack of rated current setting (RC)
Ei
Block due to “i” internal error
Vi
Block due to “I” internal voltage outside tolerance
Table 30: Block information
7.1
Description of blocks
7.1.1
“BL” Block due to water failure
In flow conditions below minimum value, with pressure lower than the set regulation value, a water failure signal is emitted and the
system shuts down the pump. The delay interval without pressure and flow can be set in the parameter TB of the TECHNICAL
ASSISTANCE menu. If the user inadvertently enters a pressure setpoint higher than the pressure that the electric pump can supply
on closure, the system indicates “block due to water failure” (BL) even if this is not precisely the problem. In this case, lower the
regulation pressure to a reasonable value, which does not normally exceed 2/3 of the head of the electrical pump installed. The
parameters SO: Dry running factor 6.5.14 and Minimum pressure pump stop due to water failure 6.5.15 enable the user to enter the
dry running protection activation thresholds.
If the parameters: SP, RC, SO and MP are not set correctly, the water failure protection will not function correctly.
7.1.2
“BPx” Block due to fault on pressure sensor
If the inverter detects a fault on the pressure sensor, the pump remains blocked and the error signal “BPx” is displayed. This status
starts as soon as the problem is detected and is reset automatically when the correct conditions are restored.
BP1 indicates an error on the sensor connected to press1, BP2 indicates an error on the sensor connected to press2,
BP3 indicates an error on the sensor connected to terminal board J5
7.1.3
"LP" Block due to low power supply voltage
Activated when the line voltage on the power supply terminal falls below the minimum admissible voltage of 295VAC. Reset is only
automatic when the voltage on the terminal exceeds 348VAC as per standard.
7.1.4
"HP" Block due to high internal power supply voltage
Activated when the internal power supply values are outside the specified range. Reset is only automatic when the voltage returns to
within the admissible values. This may be due to voltage surges or excessively brusque shutdown of the pump.
7.1.5
"SC" Block due to direct short circuit between the phases on the output terminal
The inverter is equipped with a protection against direct short circuits, which may occur between the phases U, V, and W of the
output terminal "PUMP". When this block signal is sent, the user can attempt reset by pressing b and – simultaneously
which in any event does not have any effect until 10 seconds has passed since the moment of the short circuit.
Summary of Contents for PWM 203
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...