VI. Water Piping and Trim
Figure 20: Factory Supplied Piping and Trim Installation
NOTICE
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
Install boiler so that the gas ignition system components are protected from water (dripping, spraying,
rain, etc.) during appliance operation and service (circulator replacement, etc.).
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and
can lead to boiler failure. Crown Boiler Company’ s Standard Warranty does not cover problems
caused by oxygen contamination of boiler water or scale (lime) build-up caused by frequent addition of
water.
Do not fill boiler with softened water to prevent chloride contamination.
Installation is not complete unless a safety relief valve is installed into the tapping located on left side
of appliance or the supply piping.
b. Install close nipple into tee branch, then, screw
the assembly into boiler left side front ¾ in.
tapping making sure tee run outlets are in vertical
plane and parallel to boiler side.
c. Mount ¾ in. MPT x ¾ in. FPT Pressure Relief
Valve into the tee top outlet.
d. Install Drain Valve into the tee bottom outlet.
2. Relief Valve Piping, PHNTM285 Boiler
Model
a. Locate and remove (1) ¾ in. NPT x close black
nipple, (1) ¾ in. NPT x 10 in. black nipple, ¾ in.
NPT black tee, ¾ in. FPT x ¾ in. FPT Pressure
Relief Valve, ¾ in. NPT Drain Valve.
A.
Installation of Factory Supplied Piping and
Trim Components
Phantom boilers have factory supplied Miscellaneous
Part Carton which includes supply piping components,
gas piping components, Temperature & Pressure Gauge,
Pressure Relief Valve and Drain Valve. See Figure 20
“Factory Supplied Piping and Trim Installation”.
Install these components prior to connecting boiler to
system piping as follows:
1. Relief Valve Piping, PHNTM210 Boiler
Model
a. Locate and remove ¾ in. NPT x close black
nipple, ¾ in. NPT black tee, ¾ in. MPT x ¾ in.
FPT Pressure Relief Valve, ¾ in. NPT Drain
Valve.
Notice: Required near boiler
piping (“boiler loop piping”)
size may be larger than piping/
trim supplied with boiler. See
Table 13. If larger piping is
required, increase size directly
after supplied trim.
Summary of Contents for Phantom-X PHNTM210
Page 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Page 52: ...52 VIII Electrical continued...
Page 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Page 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Page 118: ...118...
Page 119: ...119...